Example using the settings in the delivered condition
A
Start of operation with standard
room temperature
B
Set boiler water or flow tempera-
ture in accordance with the
selected heating curve
C
Set boiler water or flow tempera-
ture in accordance with coding
address "FA":
50 °C + 20 % = 60 °C
D
Duration of operation with raised
set boiler water or flow tempera-
ture in accordance with coding
address "Fb":
60 min
Remote control DIP switches
The DIP switches are located on the PCB in the top part of the casing.
Control functions
(cont.)
102
Function description
5692
673
GB