Fault
Possible cause
Remedy
In cooling mode, limited
air delivery and internal
device whistles
Ice forms at the heat ex-
changer of the internal
device due to a refrig-
eration leak
Fix leak; fill system with
refrigerant
No air delivery at the ex-
ternal unit
No voltage at the exter-
nal fan connection
Check the power supply
and connecting cable be-
tween the internal device
and the external unit
Replace PCB (external
unit)
External fan capacitor
faulty
Replace capacitor
External fan motor faulty Replace motor
In heating mode, the heat
exchanger of the external
unit is icing up
Temperature sensor of
the heat exchanger of
the external unit faulty or
incorrect connection
Check connection;
and replace the tempera-
ture sensor, if required
Controller of the external
unit faulty
Replace controller
Ice forms at the bottom of
the external unit
Condensate drain frozen
up
Connect the on-site de-
frost heater
Compressor (in the exter-
nal unit) does not run
No voltage at the term-
inals of the external unit
Check the connecting
cable between the inter-
nal device and the exter-
nal unit
Replace PCB (internal
device)
Voltage too low at the
terminals of the external
unit
Check power supply
Compressor capacitor
faulty
Replace capacitor
Compressor motor faulty Replace motor
Compressor shutdown
due to overload (low vol-
tage or high tempera-
ture)
Check voltage;
switch OFF system for
one hour
Diagnosis
(cont.)
24
Troubleshooting