No.
Fault code
Fault
Cause/Remedy
5
4
3
2
1
8
∘
●
∘
∘
∘
Processor fault exter-
nal fan
Overheating/overvoltage at
the external fan controller;
air inlet blocked; motor jum-
per incorrectly placed on the
external unit controller;
check external fan motor
9
∘
●
∘
∘
●
External fan idle
Check external fan motor
10
∘
●
∘
●
∘
Max. speed of the ex-
ternal fan exceeded
Wind-influenced excess air
inlet on the suction side; if
required, fit wind break; elec-
tromagnetic faults
11
∘
●
∘
●
●
Compressor processor
fault
Overheating/overvoltage at
the compressor speed con-
troller; air inlet blocked;
check compressor motor
12
∘
●
●
∘
∘
Compressor idle
Checking the compressor
13
∘
●
●
∘
●
Max. compressor
speed exceeded
Restart; if problem persists,
replace controller of the ex-
ternal unit
14
∘
●
●
●
∘
Excessive compressor
power consumption
Checking the compressor
15
∘
●
●
●
●
DC undervoltage
DC voltage below limit; re-
place external unit controller
16
●
∘
∘
∘
∘
DC overvoltage
Check mains voltage under
load (max. 264 V~); if OK
then replace external unit
controller
17
●
∘
∘
∘
●
AC undervoltage
Check mains voltage under
load (max. 198 V~); if OK
then replace external unit
controller
18
●
∘
∘
●
∘
No communication
Check the connecting cable
between the internal device,
the external unit and earth
...
(N/A)
22
●
∘
●
●
∘
Min. compressor
speed not achieved
Restart; if problem persists,
replace controller of the ex-
ternal unit
23
●
∘
●
●
●
System configuration
changed
For information only (com-
munication cables were
modified)