Fault
Possible cause
Remedy
Compressor overheated;
insufficient output; equip-
ment enters fault state
and compressor switches
OFF without obvious rea-
son
Electronic expansion
valve faulty
Check expansion valve
and replace, if required
Controller of the external
unit or refrigerant circuit
faulty
Scan fault code (see
page 15)
No output, although all
components operate cor-
rectly
Refrigerant leak; refrig-
erant circuit does not
function correctly
Fix leak; fill system with
refrigerant
Condensate pan of the
internal device overflows
Internal device not level
(horizontally)
Level internal device
(horizontally)
Condensate pan drain or
drain pipe blocked
Remove blockage
Drain pipe incorrectly
routed
Route the drain pipe with
a slope of at least 2 %
For cassette device:
Condensate pump does
not start
Check sensors for con-
densate level, internal
device controller and
pump
Water drips from the bot-
tom of the external unit
Condensate drain
blocked
Open external unit; re-
move blockage; clean the
bottom of the equipment
interior
One or several indicators (LED) do not function correctly
Precondition: Normal heating and cooling output.
&
Check connection between the PCB
of the internal device and the dis-
play PCB (receiver PCB on duct
mounted devices).
&
Check display PCB or receiver PCB
and replace, if required
&
Check the PCB of the internal
device and replace, if required.