No.
Fault code
Fault
Cause/Remedy
5
4
3
2
1
1
∘
∘
∘
∘
●
Room temperature
sensor not connected
Check sensor connection;
replace sensor
2
∘
∘
∘
●
∘
Room temperature
sensor short circuit
3
∘
∘
∘
●
●
Temperature sensor of
the heat exchanger of
the internal device not
connected
4
∘
∘
●
∘
∘
Short circuit of the
temperature sensor of
the heat exchanger of
the internal device
5
∘
∘
●
∘
●
Suction gas tempera-
ture sensor not con-
nected
6
∘
∘
●
●
∘
(N/A)
7
∘
∘
●
●
●
Communication error
Incompatible controllers of
the internal device and the
external unit: Replace the
controller of the internal de-
vice
8
∘
●
∘
∘
∘
No communication
Check the connecting cable
between the internal device,
the external unit and earth
9
∘
●
∘
∘
●
No code
Check fan motor connection;
replace fan motor;
Replace the controller of the
internal device
10
∘
●
∘
●
∘
(N/A)
11
∘
●
∘
●
●
External unit fault
Change over to diagnosis of
external unit
...
(N/A)
17
●
∘
∘
∘
●
Protection against
icing-up
18
●
∘
∘
●
∘
Defrost protection
19
●
∘
∘
●
●
External unit protec-
tion
Diagnosis
(cont.)
16
Troubleshooting