37
Maximum flue length
Vitodens 100-W, type B1HA and B1KA
Rated heating output
kW
19
26.0
30.0
35.0
System size 80
m
20
20
20
20
Note
For system size 80, an adaptor is
required.
Vitodens 200-W
Rated heating output
kW
13
19
26
35
System size 60
m
18
18
—
—
System size 80
m
25
25
25
25
System size 100
m
—
—
—
—
The following components are taken
into consideration for the maximum flue
lengths:
■ Balanced flue connection pipe 0.5 m
long
■ 1 flue bend 87° and 1 support bend
87°
or
■ 2 flue bends 45° and 1 support bend
87°
Subtract other bends, tees and straight
lengths from the maximum length using
the following values:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
■ Flue bend 45°: 0.3 m
■ Flue bend 87°: 0.5 m
■ Inspection tee: 0.3 m
Installation in a disused chimney
(cont.)
5780 223 GB