29
Maximum flue length
Vitodens 100-W, type B1HA and B1KA, Vitodens 111-W
Rated heating output
kW
19
26.0
30.0
35.0
System size 80
m
20
20
25
25
Note
For system size 80, an adaptor is
required.
Vitodens 200-W, 222-F and 242-F
Rated heating
output
kW
13
19
26
35
45
60
80
100
System size 60
m
18
18
—
—
—
—
—
—
System size 80
m
25
25
25
25
20
15
—
—
System size 100
m
—
—
—
—
22
17
20
20
The following components are taken
into consideration for the maximum flue
lengths:
■ Connection pipe 0.5 m long
■ 1 flue bend 87° and 1 support bend
87°
or
■ 2 flue bends 45° and 1 support bend
87°
Subtract other bends, tees and straight
lengths from the maximum length using
the following values:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
■ Flue bend 45°: 0.3 m
■ Flue bend 87°: 0.5 m
■ Inspection tee: 0.3 m
Installation
Danger
To ensure correct function, route
the flexible flue at a maximum
angle of 45° from the vertical.
Never pull the flexible flue pipe
over sharp edges during instal-
lation.
Note:
■
Always draw the flue pipe in from the
top downwards.
■
Observe flow direction (arrow on
components).
■
Subject to shaft size, install spacers
at intervals of max. 2 m.
■
Insert a spacer before and after any
change in direction and any inspec-
tion piece.
■
The flue must not come into contact
with the shaft wall.
Routing through a shaft
(cont.)
5780 223 GB