23
In conjunction with power-OFF: Load circuit (400 V~) and control circuit
(230 V~) on site
Type
Control circuit
(230 V~)
Cable cross-sec-
tion
Load circuit (400 V~)
Cable cross-section
Max. cable
length
BW 190
WW 1125
5 x 2.5 mm
2
5 x 25 mm
2
40 m
BW 1120
WW 1155
5 x 2.5 mm
2
5 x 35 mm
2
40 m
BW 2150
WW 2200
5 x 2.5 mm
2
5 x 50 mm
2
40 m
BW 2180
WW 2250
5 x 2.5 mm
2
5 x 70 mm
2
With cable terminal for
M8
40 m
BW 2250
WW 2300
5 x 2.5 mm
2
5 x 95 mm
2
With cable terminal for
M8
40 m
Note
■ The control circuit must be supplied
with power without blocking by the
power supply utility. This means a sep-
arate power supply is required for the
control circuit.
■ A separate connection for the control
circuit calls for the internal wiring to be
changed. This may only be carried out
by a heating contractor according to
the electrical wiring diagram.
■ The control circuit power supply and
the cable for the power-OFF signal can
be combined in a 5-core cable.
Line lengths in the heat pump plus wall clearance:
Type
BW
WW
Control circuit power supply (230 V~, if on-site)
2.0 m
Load circuit power supply (400 V~)
1.0 m
Additional power cables
1.5 m
Preparing for installation
Installation
(cont.)
5772 458 GB
Installation