![Viessmann VITOCAL 300-G PRO Type BW 2150 Installation And Service Instructions Manual Download Page 86](http://html1.mh-extra.com/html/viessmann/vitocal-300-g-pro-type-bw-2150/vitocal-300-g-pro-type-bw-2150_installation-and-service-instructions-manual_1017894086.webp)
86
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
■
"0"
(no cooling)
■
"2"
(natural cooling on cooling
circuit without mixer)
■
"3"
(natural cooling on cooling
circuit with mixer)
■
"4"
(active cooling)
"Cooling"
Ó
"Cooling circuit 7101"
■
"1"
(heating circuit A1/HC1)
■
"2"
(heating circuit M2/HC2)
■
"3"
(heating circuit M3/HC3)
■
"4"
(separate cooling circuit
SKK)
Instantaneous heating water heater
Parameters for
instantaneous heating water heater
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater
7900"
"1"
Poss.
"Electr booster heater"
Ó
"Enable instant. heating water heater for cen-
tral heating 7902"
"1"
"Electr booster heater"
Ó
"Output for instant. heating water heater at
power-OFF 790A"
■
"1"
for output stage 1
■
"2"
for output stage 2
■
"3"
for output stages 1 and 2
Poss.
"DHW"
Ó
"Enable electric heaters for DHW heating
6015"
"1"
External heat source
External heat source parameters
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
With circulation pump for DHW reheating:
"External heat source"
Ó
"Enable booster heaters for DHW heating
6014"
"1"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5772 458 GB