112
Operation: brine/water
Type BW
1-stage
2-stage
190
1120
2150
2180
2250
Output data
to DIN EN 14511 (B0/
W35 °C, 5 K spread)
Rated heating output
kW
93
121
150
182
240
Cooling capacity
kW
74.5
96.4
120.1
145.4
191.4
Power consumption
kW
19.5
24.8
31.9
39.6
50.4
Coefficient of performance ε
(COP)
4.77
4.83
4.70
4.60
4.76
Brine
(primary circuit)
Contents
l
33.0
42.0
55.2
69.0
89.4
Min. flow rate (spread 5 K)
l/h
15000
19000
24000
30000
39000
Pressure drop (at min. flow
rate)
mbar
120
120
130
140
180
Max. flow temperature
°C
20
20
20
20
20
Min. flow temperature
°C
–5
–5
–5
–5
–5
Heating water
(secondary
circuit)
Contents
l
227
28.7
38.7
53.5
57.1
Min. flow rate (spread 10 K) l/h
8000
10500
12900
15700
20700
Pressure drop (at min. flow
rate)
mbar
100
100
100
100
120
Max. flow temperature (at
min. flow Primary circuit
–5 °C)
°C
55
55
55
55
55
Max. flow temperature (at
min. flow Primary circuit
+5 °C)
°C
60
60
60
60
60
Operation: water/water with intermediate circuit
Type BW
1-stage
2-stage
190
1120
2150
2180
2250
Output data
to DIN EN 14511 (W10/
W35 °C, 5 K spread)
Rated heating output
kW
125
152
198
235
302
Cooling capacity
kW
104.5
128
168
197
252
Power consumption
kW
21
25.6
32.1
41
51.8
Coefficient of performance ε
(COP)
5.95
5.93
6.10
5.73
5.83
Specification
Specification, type BW 190 to BW 2250
5772 458 GB