D
■ When using hydraulic connection
accessories (connection set and
Victaulic flange adaptor set, 2½"
or 3" version):
≥ 1000 mm
■ On-site hydraulic connections:
≥ 600 mm
E
■ With fitted door hinge on the heat
pump:
≥ 910 mm
■ Without fitted door hinge on the
heat pump (removed on site):
≥ 890 mm
1000
600
D
1000
4360
E
D
Note
When installing cascades, observe the
relevant minimum clearances.
Sound attenuating plinth
Position the heat pump on a base pre-
pared on site for the purpose of noise
attenuation and uniform weight distribu-
tion.
Note
In the case of corner installation, enlarge
the base by the minimum clearances
(see previous chapter).
Preparing for installation
Installation
(cont.)