Terminals
Function
Explanation
LP1 X3.12
LP1 X3.13
or at exter-
nal exten-
sion H1
Signal "External demand"
(external starting of com-
pressor and pumps, mixer
in control operation or
OPEN, changeover of op-
erating mode of several
system components)
Requires zero volt
N/O
contact:
■ Closed: Demand
■ Open: No demand
■ Breaking capacity 230 V, 2 mA
Note
■ These or further external functions, such
as swimming pool water heating, cas-
cade or external set value default can
alternatively be connected via external
extension H1 (see installation instruc-
tions "External extension H1").
■ If a swimming pool water heating facility
is connected to external extension H1,
no other external function can be con-
nected to external extension H1.
K2 220.2
K2 220.3
Only for 2-stage heat
pumps:
Blocking compressor 2 in
connection with DHW
heating
Connection, see separate "connection and
wiring diagram" sheet 20.
STB 1
STB 2
High limit safety cut-out
(max. 70 °C) for shutting
down the secondary pump
in conjunction with an ex-
ternal heat source
Connection in series with the secondary
pump (terminal 211.2 on main PCB), see
separate "connection and wiring diagram"
sheet 20.
Installation sequence
Overview of electrical connections
(cont.)