72
Pump/component
Parameter
Setting
Remote control for
separate cooling cir-
cuit
"Cooling"
Ó
"Remote control cooling
circ 7116"
"1"
"Cooling"
Ó
"Ranking room temp
sensor separate cooling
circuit 7106"
"0"
: Room temperature sensor
connected at F16
"1"
: Vitotrol room temperature
sensor for A1/HC1
"2"
: Vitotrol room temperature
sensor for M2/HC2
"3"
: Vitotrol room temperature
sensor for M3/HC3
"4"
: Vitotrol room temperature
sensor for SKK only
See "Vitotronic 200" service in-
structions.
Vitocom 100,
type GSM
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension
"System definition"
Ó
"External extension
7010"
"1"
: EA1 extension
"2"
: AM1 extension
"3"
: EA1 and AM1 extension
Note
Parameters for external func-
tions: See the following table.
External functions
External functions
Parameter
Setting
External demand
"Internal hydraulics"
, if ap-
plicable
Ó
"Flow temperature for ex-
ternal demand 730C"
Set flow temperature
for external demand
External starting of the com-
pressor; mixer in control
mode or OPEN
"System definition"
Ó
"Effect of external demand
on heat pump/heating cir-
cuits 7014"
"0"
to
"7"
(Observe parameter
"Flow temperature
for external demand
730C"
)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5516 436 GB