77
Ventilation
Ventilation unit parameters
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Other enabling settings, if applicable:
"Ventilation"
Ó
■
"Enable preheater bank electric 7D01"
"1"
■
"Enable reheater bank hydraulic 7D02"
"1"
■
"Enable humidity sensor 7D05"
"1"
■
"Enable CO2 sensor 7D06"
"1"
If applicable, adjust values (subject to sizing):
"Ventilation"
Ó
■
"Set extract air temperature 7D08"
"100"
to
"300"
(
≙
10 to 30 °C)
■
"Flow rate reduced ventilation 7D0A"
"95"
up to
"7D0B"
minus
10 m
3
/h
■
"Flow rate nominal ventilation 7D0B"
"7D0A"
minus 10 m
3
/h up to
"7D0C"
minus 10 m
3
/h
■
"Flow rate intensive ventilation 7D0C"
"7D0B"
plus 10 m
3
/h up to
"280"
m
3
/h
Closing the heat pump
Instructing the system user
The system installer should hand the
operating instructions to the system user
and instruct the user in operating the
system.
This includes all components installed as
accessories, e.g. remote control units. In
addition, the system installer must make
the user aware of the required mainte-
nance work.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5516 436 GB
Service