113
Type AWO-AC
301.B11
301.B14
Heating output data
to EN 14511
(A2/W35)
Rated heating output
kW
7.00
8.50
Electrical power consumption
kW
1.79
2.18
Coefficient of performance ε (COP)
3.90
3.90
Heating output data
to EN 14511
(A7/W35, 5 K spread)
Rated heating output
kW
7.21
7.97
Power consumption
kW
1.44
1.59
Coefficient of performance ε (COP)
5.00
5.00
Heating output data
to EN 14511
(A–7/W35)
Rated heating output
kW
10.50
12.00
Power consumption
kW
3.38
4.00
Coefficient of performance ε (COP)
3.11
3.00
Cooling capacity data
to EN 14511
(A35/W18)
Rated cooling capacity
kW
8.10
9.00
Power consumption
kW
3.01
3.45
Energy efficiency ratio EER
2.70
2.65
Cooling capacity data
to EN 14511
(A35/W7)
Rated cooling capacity
kW
6.30
7.23
Power consumption
kW
3.15
3.71
Energy efficiency ratio EER
2.00
1.96
Heat yield
Max. fan rating at 600 rpm
W
70
70
Air volume
m
3
/h
3000
3000
Min. air intake temperature
°C
–20
–20
Max. air intake temperature
°C
35
35
Heating water
(secondary circuit)
Capacity
l
5.5
5.5
Minimum flow rate
l/h
1200
1400
Max. flow temperature at air intake tem-
perature –20 °C
°C
57
57
Max. flow temperature at air intake tem-
perature –5 °C
°C
65
65
Specification
Specification
5516 436 GB
Service