18
Required parameter settings
Parameter
Setting
"System definition"
■
"System scheme 7000"
"6"
"Compressor"
■
"Output compressor stage 5030"
Type AWB/AWB-AC
■ 201.B04:
"4"
■ 201.B07:
"7"
■ 201.B10:
"10"
■ 201.B13:
"13"
"Ext. heat source"
■
"Enable external heat source 7B00"
"1"
■
"Enable external heat source for DHW heating
7B0D"
"1"
DHW heating:
"Time program DHW heating"
Set time program (see oper-
ating instructions)
"Time program DHW circulation"
(if a DHW circulation pump is installed)
Set time program (see oper-
ating instructions)
"DHW"
■
"Enable booster heaters for DHW heating 6014" "1"
■
"Enable electric heaters for DHW heating 6015"
"1"
Instantaneous heating water heater
(if installed):
"Electr booster heater"
■
"Enable instantaneous heating water heater
7900"
"1"
■
"Enable instant. heating water heater for central
heating 7902"
"1"
Remote controls
(accessories):
"Heating circuit 1"
■
"Remote control 2003"
"1"
"Heating circuit 2"
■
"Remote control 3003"
"1"
To call up
"Coding level 1"
for setting
the parameters, see the commissioning
wizard on page 80 and page 81.
Preparing for installation
System example 1, ID: 4605169_1103_04
(cont.)
5604 692 GB