82
Disabling the service menu
The service menu remains active until it
is disabled with
"Terminate service?"
,
or if no operation takes place for 30
minutes.
Setting parameters using the "Sys-
tem scheme" example
To set a parameter, first select the
parameter group and then the parame-
ters.
All parameters are displayed as plain
text. A parameter code is also assigned
to each parameter.
Service menu:
1. Press
OK
+
å
simultaneously for
approx. 4 s
2. Select
"Coding level 1"
3. Select parameter group:
"System
definition"
4. Select parameter:
"System scheme
7000"
5. Set system scheme:
"6"
Alternatively, if the service menu was
already enabled:
Extended menu
1.
å
2.
"Service"
3. Select
"Coding level 1"
4. Select parameter group:
"System
definition"
5. Select parameter:
"System scheme"
6. Confirm parameter code:
"7000"
7. Set system scheme:
"6"
Required heat pump parameters
"Output compressor stage 5030"
During commissioning
select
the heat-
ing output of the heat pump subject to
type.
Type AWB/AWB-AC
201.B04
201.B07
201.B10
201.B13
"Output compressor stage
5030"
4 kW
7 kW
10 kW
13 kW
Required parameters for components
connected on site
Detailed explanation of param-
eters
Service instructions for Vitotronic
200 heat pump control unit
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5604 692 GB