STYLE VS1 DRY SPRINKLER INSTALLATION
FOR FIRE PROTECTION SERVICE REV_A
INTRODUCTION
Victaulic
®
VicFlex
™
Sprinkler Fittings connect the sprinkler piping directly to the sprinkler
using a flexible hose and fittings. Style VB1 Bracket Assemblies can be used with all
VS1 Sprinklers. Style VB2 Bracket Assemblies are used only with Style VS1 Recessed
Pendent Sprinklers. Style VB3 Bracket Assemblies are used only with Style VS1
Concealed Pendent Sprinklers.
•
Refer to the “Technical Data for Flexible Hoses” section.
•
Refer to the “Important Information Installation” section.
IMPORTANT INSTALLATION INFORMATION
•
DO NOT
install Style VS1 Dry Sprinklers that have been dropped or struck by
another object, even if they do not appear damaged. Never install glass bulb
sprinklers if the bulb is cracked or if there is a loss of liquid from the bulb. Discard
and replace any Style VS1 Dry Sprinklers that are damaged or show signs of
corrosion.
•
Before installation, verify that the Style VS1 Dry Sprinkler is the proper style, orifice
size, and temperature rating for the intended service.
DO NOT paint, coat, or firestop the outlet portion
DO NOT paint, coat, or firestop the inlet portion
•
DO NOT
paint, coat, or firestop the outlet/inlet portion of the Style VS1 Dry
Sprinkler, identified in the above photo. Braided hose and fitting portions of
the Style VS1 Dry Sprinkler may be painted or coated, provided that the paint
or coating is compatible with stainless steel material. This includes penetration
through firestop-filled annular space of a firewall. The firestop material in direct
contact with the flexible braided hose will not impede functionality of the Style VS1
Dry Sprinkler, provided that the components are installed in accordance with the
installation instructions featured in this section.
•
Style VS1 Dry Sprinklers that have been altered from their manufactured condition
may not function properly and may void agency listings and/or approvals.
•
DO NOT
test Style VS1 Dry Sprinklers with a heat source. The glass bulb can
weaken or shatter if exposed to a heat source during testing.
•
Style VS1 Dry Sprinklers that have operated cannot be reassembled or reused, per
NFPA requirements. When replacing sprinklers, use new sprinklers of the same
type, orifice, temperature, and response.
•
DO NOT
clean Style VS1 Dry Sprinklers with soapy water, detergents, ammonia,
cleaning fluids, or other chemicals. Remove any dust, lint, etc. with a soft, dry
cloth.
•
Inspect Style VS1 Dry Sprinklers on a regular basis for corrosion, mechanical
damage, obstructions, etc. The frequency of inspections may vary due to corrosive
atmospheres/water supplies and activities around the sprinklers.
•
DO NOT
hang anything from or attach anything to Style VS1 Dry Sprinklers.
Obstructing the discharge pattern will prevent the sprinkler from operating properly.
Summary of Contents for VicFlex AB12
Page 2: ......
Page 10: ...I VICFLEX_10 This page intentionally left blank...
Page 11: ...I VICFLEX_11 General Information...
Page 16: ...I VICFLEX_16 This page intentionally left blank...
Page 17: ...I VICFLEX_17 Construction Requirements...
Page 20: ...I VICFLEX_20 This page intentionally left blank...
Page 21: ...I VICFLEX_21 Styles AB1 AB2 and AB10 Brackets Installation Instructions...
Page 34: ...I VICFLEX_34 This page intentionally left blank...
Page 35: ...I VICFLEX_35 Style AB3 Bracket Installation Instructions...
Page 39: ...I VICFLEX_39 Style AB4 Bracket Installation Instructions...
Page 43: ...I VICFLEX_43 Style AB5 Bracket Installation Instructions...
Page 50: ...I VICFLEX_50 This page intentionally left blank...
Page 51: ...I VICFLEX_51 Style AB6 Bracket Installation Instructions...
Page 61: ...I VICFLEX_61 Style AB7 Bracket Installation Instructions...
Page 68: ...I VICFLEX_68 This page intentionally left blank...
Page 69: ...I VICFLEX_69 Style AB11 Bracket Installation Instructions...
Page 73: ...I VICFLEX_73 Style AB12 Bracket Installation Instructions...
Page 79: ...I VICFLEX_79 ABBA ABMM Bracket Installation Instructions...
Page 86: ...I VICFLEX_86 This page intentionally left blank...
Page 87: ...I VICFLEX_87 Style AQC U Bracket Installation Instructions...
Page 92: ...I VICFLEX_92 This page intentionally left blank...
Page 93: ...I VICFLEX_93 Style C AQC Bracket Installation Instructions...
Page 96: ...I VICFLEX_96 This page intentionally left blank...
Page 97: ...I VICFLEX_97 Style AQD M Bracket Installation Instructions...
Page 104: ...I VICFLEX_104 This page intentionally left blank...
Page 105: ...I VICFLEX_105 Style AQD Bracket Installation Instructions...
Page 113: ...I VICFLEX_113 VS1 Dry Sprinkler Installation Instructions...
Page 128: ...I VICFLEX_128 This page intentionally left blank...
Page 129: ...I VICFLEX_129 Connection to the Sprinkler Piping...
Page 139: ...I VICFLEX_139 Connecting the Sprinkler Reducing Nipple to the Flexible Hose...
Page 141: ...I VICFLEX_141 Sprinkler Reducing Nipple Installation...
Page 148: ...I VICFLEX_148 This page intentionally left blank...
Page 149: ...I VICFLEX_149 Sprinkler Installation...
Page 151: ...I VICFLEX_151 Victaulic VicFlex Tamper Evident Labels Application Instructions...
Page 154: ...I VICFLEX_154 This page intentionally left blank...
Page 155: ...I VICFLEX_155 Minimum Bend Radius Guides...
Page 202: ......
Page 203: ......