TECHNICAL DATA FOR FLEXIBLE HOSES REV_A
SERIES AH1, AH1-CC, AH1-LP, AND AH1-CC-LP
FLEXIBLE HOSE FRICTION LOSS DATA (VDS)
NOTICE
• The following table contains VDS friction loss data. Always refer to the
applicable “Listing and Approval Information – Flexible Hose and Bracket
Combinations” section to verify the listings/approvals for the particular flexible
hose/bracket combination.
Length of
Flexible Hose
mm/
inches
Outlet
Size
Metric/
inches
Equivalent Length of
Steel Pipe in meters/
feet According to
EN 10255 DN20
(26,9 x 2,65)
Maximum Number
of 90° Bends at
76.2-mm/3-inch
Bend Radius
790
31
DN15/1/2
3.2
10.5
3
DN20/3/4
915
36
DN15/1/2
3.7
12.1
3
DN20/3/4
1220
48
DN15/1/2
4.9
16.1
3
DN20/3/4
1525
60
DN15/1/2
6.1
20.0
4
DN20/3/4
1830
72
DN15/1/2
7.3
24.0
4
DN20/3/4
Only VdS Approved pendent spray sprinklers of 10-mm, 15-mm, and 20-mm nominal diameters with
K-factors of 57, 80, and 115 shall be used.
•
Tested with a 5 3/4-inch/146-mm length straight reducer.
•
When using a No. 101 90° Elbow or a No. 102 Straight Tee in place of a Style 108 Coupling on
the end of a Series AH1-CC or AH2-CC Flexible Hose, the friction loss data shown above shall
be added to the No. 101 or No. 102 friction loss data published in Victaulic
®
submittal 10.54.
•
Flexible Hoses are VdS Approved for use in wet systems only.
NOTE
: The VdS Approval applies only for use with specific suspended ceiling systems. Refer to the
“Construction Requirements” section of this handbook.
•
Other manufacturers’ ceiling systems, with comparable or better performance, can be
considered for approval.
•
VdS standards for safety include, but are not limited to: pressure cycling, corrosion resistance,
flow characteristics, vibration resistance, leakage, mechanical strength, and hydrostatic
strength.
•
Differences in equivalent lengths are due to varying test methods, per FM 1637 and VdS
standards. Refer to these standards for additional information regarding friction loss test
methods.
Summary of Contents for VicFlex AB12
Page 2: ......
Page 10: ...I VICFLEX_10 This page intentionally left blank...
Page 11: ...I VICFLEX_11 General Information...
Page 16: ...I VICFLEX_16 This page intentionally left blank...
Page 17: ...I VICFLEX_17 Construction Requirements...
Page 20: ...I VICFLEX_20 This page intentionally left blank...
Page 21: ...I VICFLEX_21 Styles AB1 AB2 and AB10 Brackets Installation Instructions...
Page 34: ...I VICFLEX_34 This page intentionally left blank...
Page 35: ...I VICFLEX_35 Style AB3 Bracket Installation Instructions...
Page 39: ...I VICFLEX_39 Style AB4 Bracket Installation Instructions...
Page 43: ...I VICFLEX_43 Style AB5 Bracket Installation Instructions...
Page 50: ...I VICFLEX_50 This page intentionally left blank...
Page 51: ...I VICFLEX_51 Style AB6 Bracket Installation Instructions...
Page 61: ...I VICFLEX_61 Style AB7 Bracket Installation Instructions...
Page 68: ...I VICFLEX_68 This page intentionally left blank...
Page 69: ...I VICFLEX_69 Style AB11 Bracket Installation Instructions...
Page 73: ...I VICFLEX_73 Style AB12 Bracket Installation Instructions...
Page 79: ...I VICFLEX_79 ABBA ABMM Bracket Installation Instructions...
Page 86: ...I VICFLEX_86 This page intentionally left blank...
Page 87: ...I VICFLEX_87 Style AQC U Bracket Installation Instructions...
Page 92: ...I VICFLEX_92 This page intentionally left blank...
Page 93: ...I VICFLEX_93 Style C AQC Bracket Installation Instructions...
Page 96: ...I VICFLEX_96 This page intentionally left blank...
Page 97: ...I VICFLEX_97 Style AQD M Bracket Installation Instructions...
Page 104: ...I VICFLEX_104 This page intentionally left blank...
Page 105: ...I VICFLEX_105 Style AQD Bracket Installation Instructions...
Page 113: ...I VICFLEX_113 VS1 Dry Sprinkler Installation Instructions...
Page 128: ...I VICFLEX_128 This page intentionally left blank...
Page 129: ...I VICFLEX_129 Connection to the Sprinkler Piping...
Page 139: ...I VICFLEX_139 Connecting the Sprinkler Reducing Nipple to the Flexible Hose...
Page 141: ...I VICFLEX_141 Sprinkler Reducing Nipple Installation...
Page 148: ...I VICFLEX_148 This page intentionally left blank...
Page 149: ...I VICFLEX_149 Sprinkler Installation...
Page 151: ...I VICFLEX_151 Victaulic VicFlex Tamper Evident Labels Application Instructions...
Page 154: ...I VICFLEX_154 This page intentionally left blank...
Page 155: ...I VICFLEX_155 Minimum Bend Radius Guides...
Page 202: ......
Page 203: ......