I-VICFLEX_54
STYLE AB6 BRACKET INSTALLATION FOR
FIRE PROTECTION SERVICE REV_A
TEMPERATURE MAINTAINED AT 60°F/16°C MINIMUM
Ambient Temperature
Exposed to Discharge
End of Sprinkler
“D” Freezer Ceiling or
Wall Thickness
“A” Order Length
Down to 20°F
3 – 6 inch/76 – 152 mm
12 inch/305 mm
Down to -6.7°C
7 – 12 inch/178 – 305 mm
18 inch/457 mm
19°F to 0°F
3 – 6 inch/76 – 152 mm
12 inch/305 mm
-7.2°C to -17.8°C
7 – 12 inch/178 – 305 mm
18 inch/457 mm
-1°F to -20°F
3 – 6 inch/76 – 152 mm
12 inch/305 mm
-18.3°C to -28.9°C
7 – 12 inch/178 – 305 mm
18 inch/457 mm
-21°F to -30°F
3 – 6 inch/76 – 152 mm
12 inch/305 mm
-29.4°C to -34.4°C
7 – 12 inch/178 – 305 mm
18 inch/457 mm
-31°F to -40°F
3 – 6 inch/76 – 152 mm
12 inch/305 mm
-35.0°C to -40.0°C
7 – 12 inch/178 – 305 mm
18 inch/457 mm
Product Marking Information
UL 2443 Model
Designation
Outlet
Fitting Mark
Description
AH2-XX-AB6
AB6
AH2 with Style AB6 Bracket Assembly and
V33, V36, or V40 Dry Sprinkler
AH2-CC-XX-AB6
AB6
AH2-CC with Style AB6 Bracket Assembly and
V33, V36, or V40 Dry Sprinkler
NOTE:
Flexible hoses are marked with all UL model designations. In addition, the outlet fitting
of the flexible hose is marked with the model’s corresponding suffix designation, if applicable.
Refer to the chart above to correlate the markings with the UL Listing.
Summary of Contents for VicFlex AB12
Page 2: ......
Page 10: ...I VICFLEX_10 This page intentionally left blank...
Page 11: ...I VICFLEX_11 General Information...
Page 16: ...I VICFLEX_16 This page intentionally left blank...
Page 17: ...I VICFLEX_17 Construction Requirements...
Page 20: ...I VICFLEX_20 This page intentionally left blank...
Page 21: ...I VICFLEX_21 Styles AB1 AB2 and AB10 Brackets Installation Instructions...
Page 34: ...I VICFLEX_34 This page intentionally left blank...
Page 35: ...I VICFLEX_35 Style AB3 Bracket Installation Instructions...
Page 39: ...I VICFLEX_39 Style AB4 Bracket Installation Instructions...
Page 43: ...I VICFLEX_43 Style AB5 Bracket Installation Instructions...
Page 50: ...I VICFLEX_50 This page intentionally left blank...
Page 51: ...I VICFLEX_51 Style AB6 Bracket Installation Instructions...
Page 61: ...I VICFLEX_61 Style AB7 Bracket Installation Instructions...
Page 68: ...I VICFLEX_68 This page intentionally left blank...
Page 69: ...I VICFLEX_69 Style AB11 Bracket Installation Instructions...
Page 73: ...I VICFLEX_73 Style AB12 Bracket Installation Instructions...
Page 79: ...I VICFLEX_79 ABBA ABMM Bracket Installation Instructions...
Page 86: ...I VICFLEX_86 This page intentionally left blank...
Page 87: ...I VICFLEX_87 Style AQC U Bracket Installation Instructions...
Page 92: ...I VICFLEX_92 This page intentionally left blank...
Page 93: ...I VICFLEX_93 Style C AQC Bracket Installation Instructions...
Page 96: ...I VICFLEX_96 This page intentionally left blank...
Page 97: ...I VICFLEX_97 Style AQD M Bracket Installation Instructions...
Page 104: ...I VICFLEX_104 This page intentionally left blank...
Page 105: ...I VICFLEX_105 Style AQD Bracket Installation Instructions...
Page 113: ...I VICFLEX_113 VS1 Dry Sprinkler Installation Instructions...
Page 128: ...I VICFLEX_128 This page intentionally left blank...
Page 129: ...I VICFLEX_129 Connection to the Sprinkler Piping...
Page 139: ...I VICFLEX_139 Connecting the Sprinkler Reducing Nipple to the Flexible Hose...
Page 141: ...I VICFLEX_141 Sprinkler Reducing Nipple Installation...
Page 148: ...I VICFLEX_148 This page intentionally left blank...
Page 149: ...I VICFLEX_149 Sprinkler Installation...
Page 151: ...I VICFLEX_151 Victaulic VicFlex Tamper Evident Labels Application Instructions...
Page 154: ...I VICFLEX_154 This page intentionally left blank...
Page 155: ...I VICFLEX_155 Minimum Bend Radius Guides...
Page 202: ......
Page 203: ......