16 STAGE APPLICATION
R851V-8 MASTER UNIT, R851V-4 SLAVE UNIT ( See also slave application section at the end )
R851V-8 Master Unit Control Switch
R851V-8 Slave Unit Control Switch
Number
of stage
Switch #3
Switch #4
Switch #5
Switch #6
Switch #3
Switch #4
Switch #5
Switch #6
9
Off
Off
Off
On
Off
Off
Off
Off
10
On
Off
Off
On
On
Off
Off
Off
11
Off
On
Off
On
Off
On
Off
Off
12
On
On
Off
On
On
On
Off
Off
13
Off
Off
On
On
Off
Off
On
Off
14
On
Off
On
On
On
Off
On
Off
15
Off
On
On
On
Off
On
On
Off
16
On
On
On
On
On
On
On
Off
The intensity of the yellow status LED on the master unit is proportional to the slave output.
R851V DIMENSIONS & INSTALLATION
Install on the mounting plate on the electrical cabinet using five #6 pan head metal screw. Do not over torque the screws to prevent
damage to the board. Specifications and equipment are subject to change without prior notice.
All R851V series controls are for use only as operating controls. Whenever a control failure could lead to personal
injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system
to protect against such catastrophic failures.
Note: Set all control signal INPUT
dip switch to
OFF
on slave unit.