8 STAGE APPLICATION
R851V-8
R851V-8 Control Switch
Number of
stage
Switch #3
Switch #4
Switch #5
Switch #6
1
Off
Off
Off
Off
2
On
Off
Off
Off
3
Off
On
Off
Off
4
On
On
Off
Off
5
Off
Off
On
Off
6
On
Off
On
Off
7
Off
On
On
Off
8
On
On
On
Off
•
12 STAGE APPLICATION
R851V-8 MASTER UNIT, R851V-4 SLAVE UNIT ( See also slave application section at the end )
R851V-8 Master Unit Control Switch
R851V-4 Slave Unit
Number
of stage
Switch #3
Switch #4
Switch #5
Switch #6
Switch #3
Switch #4
9
Off
Off
Off
On
Off
Off
10
On
Off
Off
On
On
Off
11
Off
On
Off
On
Off
On
12
On
On
Off
On
On
On
The intensity of the yellow status LED on the master unit is proportional to the slave output.
1
2
3
1
2
3
ON
4
5
6
O N T R O L
1
2
3
ON
4
I N P U T C
1
2
3
O N T R O L
1
2
3
ON
4
I N P U T C
20
0
1
2
3
ON
4
Note: Set all control signal INPUT
dip switch to
OFF
on
slave unit.