2

2 To 10 Vdc Or 0 To 10 Vdc Stand Alone Thermostat

( Power To The Thermostat Is Supplied By The R851V )

0 To 135

 Stand Alone Thermostat

2 To 10 Vdc Or 0 To 10 Vdc From D.D.C.

Building Automation System

4 To 20 mA From D.D.C.

Building Automation System

24 VAC POWER & RELAY OUTPUT WIRING                                                                                                                            

The wiring diagrams are for the R851V-8 models with 8 outputs. The wiring for the R851V-4 is the same except that the unit only
has 4 outputs.

Terminals

Screw terminal & connector #1

Common

Screw terminal & connector #2

24 Vac

Screw terminal & connector #3

Control Signal input

 

It is not necessary to ground any leg of the transformer to earth with the controller card.

 

The controller uses internally a half wave rectifier bridge. On 0 to 10 Vdc control signal, the reference of the control signal is the
Common of the power supply of the SCR controller card.

 

Use a Class 1 ( properly fused ) or Class 2,  CSA or UL recognized transformer.

4 STAGE APPLICATION

R851V-4

R851V-4 Control Switch

Number of

stage

Switch #3

Switch #4

1

Off

Off

2

On

Off

3

Off

On

4

On

On

Common

24 Vac

0 to 10 Vdc

output

2 Vdc = 0% capacity

10 Vdc = 100% capacity

1

2

3

1

1

2

3

ON

4

I N P U T

R

W

B

0 Ohms = 0% capacity

135 Ohms = 100% capacity

1

2

3

1

1

2

3

ON

4

I N P U T

-

+

2 Vdc = 0% capacity

10 Vdc = 100% capacity

1

2

3

1

1

2

3

ON

4

I N P U T

4 mA = 0% capacity

20 mA = 100% capacity

-

+

1

2

3

1

1

2

3

ON

4

I N P U T

1

2

3

1

2

3

ON

4

O N T R O L

1

2

3

ON

4

I N P U T C