VERNIER STAGE WIRING

Control Switch #2 On

Vdc pulsed to activate R810 power modules

Do not wire more than six R810 power module on the
vernier stage output

Respect the polarity between the R851 step controller
board an the R810 power modules

Connect       

V

 to 

+

Connect       

COM

 to 

-

The green status LED on the master unit will cycle at
the same rate as the time proportioning vernier output

For more information, please refer to the R810 service
manual

Control Switch #2 Off

0 to 10 Vdc analog output to activate R820 SCR power controller

Set the 

R820 SCR

 power controller to accept a 0 to 10 Vdc control signal input

Switch 

#1, #2 & #3  O

ff       Switch 

#4 On

The intensity of the green status LED on the master unit is proportional to vernier output
For more information, please refer to the R820 service manual

SLAVE APPLICATION SECTION                                                                                                                                              

When using a unit for slave applications, it is important that the proper adjustments & setting be made to the unit for proper
operation of the system.
The yellow LED near the vernier output connector is proportional to the vernier output of the master unit ( 0 to 5 Vdc ).

On the slave unit:

 

Set vernier ratio potentiometer to 100%

 

Set interstage delay potentiometer to the same value as the master unit

 

Set all control signal 

INPUT 

dip switch to 

OFF

TEST MODE BUTTON                                                                                                                                                               

The test mode button can be used to verify if the number of stage have been configured properly.

1.  Press and hold the button for 3 to 4 seconds.
2.  If a slave unit is used, press & hold the 2 units button simultaneously
3.  All the selected stage will come on, one after the other until all selected number of stages are all on.
4.  There is a delay of approximately 5 second between each step activation.
5.  When all selected stage are on, they will stay on for approximately 30 seconds before shutting down.

Powering up the R851V controller while holding down the test button will by-pass the interstage delay for 10 minutes. During that
period, the unit will respond to a changing signal input very rapidly. Also hold down slave test button on start-up if a slave unit is
used.  After that 10 minute period, the unit will function normally with the interstage delays active

Viconics Electronics Inc.

9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9

www.viconics.com

[email protected]

LIT-R851V-E03

1

2

3

1

2 3

ON

4

I N P U T

CO

M

V

S

+

-

R810

1 2 3

R820
SCR Power Controller

1 2 3

1

2

3

ON

4

5

6

ONT ROL

1

2

3

ON

4

I NPUT C

028-5009 – REV.2

Reviews: