2.2.2 Analog I/O module - Outputs
Each channel supports eight output signals on a 14-position panel header with a mating connector.
•
Raw Out:
Analog outputs that represent the processed raw signal from the sensor on the corresponding
input channel.
Important Information
•
Raw and Trend outputs (4/20 mA) do not require power from an external source.
•
Trend Out:
Analog outputs representing the selected processed signal from the sensor on the corresponding
input channel.
•
Voltage Output (Raw, and Trend)
- Output range:
0 to 10V
- Load: 10 kΩ min.
- Processing range: According to ZOOM Configuration
•
Current Output (Raw, and Trend)
- Output range:
4 to 20 mA
- Load: 500 Ω max.
- Processing range: According to ZOOM Configuration
ZPU-5000 Acquisition and Processing Unit with ZOOM Version 7.4 - User’s Manual
21