5.2.3
Setting of the boiler control unit
Detailed information on the control unit is specified in a separate manual “VERA BORD 360. Control unit”
5.2.3.1
Boiler power settings
WARNING!!!
Before commissioning the boiler, it is necessary to set boiler power. Parameter “Boiler model”
The minimal and maximal rpm of the ventilator are preset in the control unit (it means the boiler power). Each boiler size has different values. It
is necessary to set the boiler power according to the rated value.
Push-button press
(min 3 seconds)
Service menu
enter the code 2003
Boiler settings
Boiler model
Choose a correct power row
press the START push-button
(YES)
Tab. №. 6
Preset values
Boiler model
15 kW
18 kW
23 kW
27 kW
34 kW
Max. rotation speed of the ventilator
15 %
25 %
35 %
40 %
60 %
Min. rotation speed of the ventilator
15 %
20 %
25 %
30 %
50 %
WARNING!!!
When activating the parameter “Renewal of factory settings”, boiler power is returned onto the factory
settings. (Factory settings of 15 kW) According to data on the production label of the boiler - Rated heat power has to
be
set again “Boiler model”.
5.2.3.2
Perform remaining setting according to the heating system and the boiler type.
Detailed information of the control unit is in a separate manual “Control unit VERA BORD 360”.
Service menu
Boiler settings
Boiler model
15 kW
16 kW
23 kW
27 kW
34 kW
18 kW
30 kW