6 Initial Operation
For selecting the ‘main menu’ press ENTER.
For navigation in ‘main menu’ and submenus use the UP and
DOWN.
To enter the chosen submenu press ENTER again.
1 'up'
info screen, raise values, scroll up
2 'left'
set unit to remote/local operation,
move cursor to left
3 'enter'
enter menu, confirm selection
4 'right'
set unit ON/OFF,
move cursor to right
5 'down'
lower values, scroll down
6 LED 'System OK'
7 LED 'Warning'
8 LED 'Alarm'
9 SD-Card Slot
for system update
10 base panel terminal
standard RJ-45 connector, use CAT5e patch cable
For leaving any menu item
move the cursor to ‘exit’ and press ENTER.
For changing values or shifting the cursor use buttons UP, DOWN and RIGHT, LEFT.
Power the system
Switch on main switch or connect power plug à system remains in standby mode
Switching ON the system
Press button RIGHT
to enter the ‘System ON/OFF’ menu
Move in me
nu to ‘system on’ by button DOWN and press button ENTER to start lamp operation
à The UV lamps will be operated with its nominal operation
parameter. System status indication:
frontend à LCD message
‘system on’ and ‘all lamps on’
base unit à
LEDs ‘lamp A, B, C’ are on
Switching OFF the system
Press button RIGHT
to enter the ‘System ON/OFF’ menu
Move to ‘system off’ by button DOWN and press button ENTER to stop lamp operation
à The UV lamps will be stopped after the shutdown delay is expired. (factory default 30
sec.) System status indication:
frontend à LCD message
‘system off’ and ‘all lamps off’ base
unit à no lamp LED is on
Please note:
If system was switched off by main switch and then is switched on again, the system will go back to the
previous state.