Automatic change-over device type IVPS

      ENGLISH

Operation

The  Automatic  change  over  device  switches  automatically 
between the three AC sources.
The  input  is  taken  from  output  of  Generator,  Shore  Power  and 
Inverter. In case of failure of generator the shore power will take-
over. If shore power and generator fail, inverter will take over. 

The  Vetus  IVPS  has  a  built-in  micro  controller  to  control  the 
relays  and  indicators.  The  micro  controller  is  used  to  choose 
the  best  source  of  power  based  on  two  choices:  the  prior-
ity  of  the  power  source,  and  the  voltage  of  the  power  source. 
For  example,  if  the  shore  power  and  generator  are  both  avail-
able, the generator power will have priority. But if the voltage of 
the generator power is too low or too high, then the priority of 
the generator is not considered, and the shore power is used. 
The  acceptable  voltage  of  the  shore  power  and  generator  is 
230  V  AC  –20%  and  +10%.  This  means  the  voltage  must  be 
between 184 V and 253 V.

In case the output is switched to shore power or inverter and the 
generator is switched-on (manual) a delay can be a set to give 
the generator time to start-up. Generator time delay is adjustable 
from 1 to 30 seconds.

5.1. LED indicators

LED

FUNCTION

Generator IN

ON:

Generator  is ON

Generator OUT

ON:

Output powered by generator

Shore Power IN

ON:

Shore Power is ON

Shore Power OUT

ON:

Output powered by shore 
power

Inverter IN

ON:

Inverter is ON

Inverter OUT

ON:

Output powered by inverter

Malfunctions

Malfunction /indication

Possible  cause

Solution

 LED ‘Generator IN’ off

No output from the generator.

Switch ON the generator and check the output.

Connection fault.

Check the connections of the generator to IVPS.

LED printed circuit board connection 
broken.

Contact service department.

 LED ‘Shore power IN’ off

No output from the shore power.

Switch ON the shore power and check the output.

Connection fault.

Check the connections of the shore power to IVPS.

 LED ‘Inverter IN’ off

No output from the inverter.

Switch ON the inverter and check the output.

Connection fault.

Check the connections of the inverter to IVPS.

LED ‘Generator IN’ on,
But output powered from Shore 
Power

Generator output voltage is not within 
the limits (too low or high)

Check voltage of the generator.

Module fault.

Contact service department.

LED ‘Shore power’ on But 
output powered from the 
inverter.

Shore power output voltage is not 
within the limits (too low or high)

Check the voltage of the shore power.

Module fault.

Contact service department.

Technical data

Type 

: IVPS

Function 

: Automatic switching system between generator or shore power or Inverter 

Capacity 

: 4.5 kVA maximum

Nominal voltage 

: 230V AC

Accepted voltage of generator and shore power  : -20% and +10% (higher than 184 V, lower than 253 V
Frequency 

: 50Hz

Time delay 

: Switching delay to generator mode is adjustable between 1-30 Sec 

Dimensions 

: 290 x 180 x 95 mm

Weight 

: 2.4 kg

Summary of Contents for IVPS

Page 1: ...s Bedienungshandbuch und Installationsvorschriften Manuel d utilisation et instructions d installation Manual de uso e instrucciones de instalación Manuale d uso e istruzioni per l installazione 4 6 8 10 12 14 IVPS Omschakelautomaat Automatic change over device Automatischer Umschalter Commutateur automatique Activador automático Commutatore automatico ...

Page 2: ...0082 1 y 73 23 EEC Directiva Baja Tensión EN60335 1 Questo prodotto è conforme alle direttive comunitarie 89 336 EEC EMC EN50081 1 EN50082 1 e 73 23 EEC Direttiva Bassa Tensione EN60335 1 Inhoud 1 Inleiding 4 2 Informatie voor de gebruiker 4 2 1 Doel van de handleiding 4 2 2 Verklaring van de tekens 4 3 Voor uw veiligheid 4 3 1 Algemeen 4 3 2 Gebruik 4 4 Installatie 4 4 1 Installeren 4 4 2 Aanslui...

Page 3: ...ts 11 7 Spécifications techniques 11 8 Schémas de raccordements 16 9 Block schéma 18 10 Dimensions principales 19 Índice 1 Introducción 12 2 Información para el usuario 12 2 1 Objetivo de este manual 12 2 2 Descripción de los símbolos 12 3 Para su seguridad personal 12 3 1 General 12 3 2 Uso 12 4 Instalación 12 4 1 Instalar 12 4 2 Conexiones 12 5 Funcionamiento 13 5 1 I ndicadores LED 13 6 Fallos ...

Page 4: ...van de fabrikant leverancier 3 2 Gebruik De IVPS mag alleen worden gebruikt als deze zich in perfecte staat bevindt Indien storingen optreden die de veiligheid van de gebruiker en of het schip in gevaar kunnen brengen dient de IVPS onmiddellijk uitgeschakeld te worden Om veiligheids reden is het verboden om aanpassingen aan te brengen aan de IVPS Reparaties zoals het vervangen van de zekering moge...

Page 5: ...om staat AAN Shore Power OUT AAN Uitgang gevoed door wal stroom Inverter IN AAN Omvormer staat AAN Inverter OUT AAN Uitgang gevoed door omvor mer 6 Storingen Storing aanwijzing Mogelijke oorzaak Oplossing LED Generator IN staat uit Geen uitvoer uit generator Schakel de generator in en controleer de uitvoer Aansluitingsfout Controleer de aansluitingen van de genera tor op de IVPS Aansluiting LED pr...

Page 6: ...all forms of guarantee and liability of the manufacturer supplier will lapse 3 2 Use The IVPS may only be used in technically perfect condition If malfunctions occur that can affect the safety of user and ship the IVPS must immediately be turned off For safety reasons amendments to the apparatus are prohibited Repairs e g replacing the fuse may only be carried out by persons skilled in such Safety...

Page 7: ...er is ON Shore Power OUT ON Output powered by shore power Inverter IN ON Inverter is ON Inverter OUT ON Output powered by inverter 6 Malfunctions Malfunction indication Possible cause Solution LED Generator IN off No output from the generator Switch ON the generator and check the output Connection fault Check the connections of the generator to IVPS LED printed circuit board connection broken Cont...

Page 8: ...Haftung seitens des Herstellers Lieferanten 3 2 Benutzung Der automatische Umschalter darf nur benutzt werden wenn er sich in einem technisch einwandfreien Zustand befindet Treten Fehlfunktionen auf die die Sicherheit des Benutzers und Schiffs beeinträchtigen können muss der automatische Umschalter sofort ausgeschaltet werden Aus Sicherheitsgründen ist es verboten Änderungen am Gerät vorzunehmen R...

Page 9: ...UT AN Ausgangsversorgung über Kaistrom Inverter IN AN Inverter ist AN Inverter OUT AN Ausgangsversorgung über Inverter 6 Fehlfunktionen Fehlfunktion Anzeige Mögliche Ursache Lösung LED Generator IN aus Keine Ausgangsleistung vom Generator Generator einschalten und Ausgangsleistung über prüfen Fehlerhafter Anschluss Anschlüsse Generator an Umschalter überprüfen Verbindung zur LED Leiterplatine unte...

Page 10: ...e garantie ainsi que la responsabilité du fabricant fournis seur seront annulées 3 2 Utilisation L IVPS ne peut être utilisé que s il est en parfait état technique Si des dysfonctionnements susceptibles de mettre la sécurité de l utilisateur et du bateau en danger se produisent l IVPS doit être mis directement hors service Il est interdit pour des raisons de sécurité d effectuer des modi fications...

Page 11: ... power IN Allumé Courant du quai sur ON Shore power OUT Allumé La sortie est alimentée par le courant du quai Inverter IN Allumé Inverseur sur ON Inverter OUT Allumé La sortie est alimentée par l inverseur 6 Dysfonctionnements Panne indication Cause possible Solution LED Generator IN éteint Rien ne sort du générateur Allumer le générateur et vérifier la sortie Erreur de raccordement Vérifier le ra...

Page 12: ...be usarse en perfectas condiciones técnicas Si se observan funcionamientos anómalos que puedan afectar a la seguridad del usuario y de la embarcación deberá desconec tar inmediatamente el IVPS Por motivos de seguridad queda prohibida cualquier modificación del aparato Las reparaciones por ej el cambio del fusible únicamente pueden ser llevadas a cabo por técnicos cualificados Se deben efectuar las...

Page 13: ...imentación de puerto Inverter IN ON El convertidor está activado Inverter OUT ON Salida alimentada por el con vertidor 6 Fallos de funcionamiento Fallo indicación Posible causa Solución LED Generator IN apagado Sin salida del generador Conecte el generador y compruebe la salida Fallo de conexión Compruebe las conexiones del generador con el IVPS Conexión de circuito impreso de LED rota Contacte co...

Page 14: ... deve essere usato solo in condizioni tecniche perfette In caso di malfunzionamenti che possono influire sulla sicurezza dell utilizzatore e dell imbarcazione l IVPS deve essere spento immediatamente Per ragioni di sicurezza è vietato effettuare revisioni dell apparecchio Eventuali riparazioni per es la sosti tuzione del fusibile devono essere effettuate esclusivamente da personale competente Il c...

Page 15: ...zione in banchina è accesa Shore power OUT ACCESO Uscita alimentata dalla banchina Inverter IN ACCESO L inverter è acceso Inverter OUT ACCESO Uscita alimentata dall inverter 6 Malfunzionamenti Malfunzionamento indica zione Possibile causa Rimedio LED Generator IN spento Nessuna uscita dal generator Accendere il generatore e controllare l uscita Errore di connessione Controllare le connessioni tra ...

Page 16: ...ingang 4 Ausgang 5 Einstellung Generatorzeitverzögerung 1 Entrée inverseur 2 Entrée courant du quai 3 Entrée générateur 4 Sortie 5 Réglage du délai pour le générateur 1 Entrada de convertidor 2 Entrada de toma de alimentación de puerto 3 Entrada de generador 4 Salida 5 Ajustes de demora de tiempo del generador 1 Ingresso inverter 2 Ingresso alimentazione in banchina 3 Ingresso generatore 4 Uscita ...

Page 17: ...oard network 230 V 1 Generatorset 2 Kaianschluss 230 V 3 Umformer 4 Automatischer Umschalter IVPS 5 Bordstromnetz 230 V 1 Générateur 2 Réseau du quai 230 V 3 Onduleur 4 Commutateur automatique IVPS 5 Circuit de bord 230 V 1 Grupo electrógeno 2 Conexión a tierra 230 V 3 Convertidor 4 Activador automático IVPS 5 Red de a bordo 230 V 1 Generatore 2 Collegamento alla banchina 230 V 3 Trasformatore 4 C...

Page 18: ...ion 230 V 3 Inverter 4 Delay 5 Controller 6 Relays 7 Output indicators 8 Output 9 Input indicators 1 Generatorset 2 Kaistromanschluss 230 V 3 Inverter 4 Verzögerung 5 Prozessor 6 Relais 7 Ausgangsanzeigen 8 Ausgang 9 Eingangsanzeigen 1 Générateur 2 Raccordement du quai 230 V 3 Inverseur 4 Délai 5 Contrôleur 6 Relais 7 Témoins de sortie 8 Sortie 9 Témoins d entrée 1 Grupo electrógeno 2 Conexión de ...

Page 19: ...c change over device type IVPS i 180 290 95 116 29 5 29 5 15 268 ø 5 175 275 87 5 87 5 ø 5 1 2 5 Hoofdafmetingen Principal dimensions Hauptabmessungen Dimensions principales Dimensiones principales Dimensioni principali 10 ...

Page 20: ...FOKKERSTRAAT 571 3125 BD SCHIEDAM HOLLAND TEL 31 10 4377700 TELEX 23470 TELEFAX 31 10 4372673 4621286 E MAIL sales vetus nl INTERNET http www vetus com Printed in India 090131 01 03 06 ...

Reviews: