Table 6:
Typical Input Data with 60 Hz Input
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
120
0
0.233
28.132
4.863
0.17286
--
16.59
25
2.175
262.037
256.726
0.97973
90.76
80.96
50
4.185
503.75
499.92
0.99241
93.09
117.85
75
6.278
754.97
751.24
0.99505
92.94
181.02
100
--
--
--
--
--
--
110
--
--
--
--
--
--
208
0
0.34
67.243
4.713
0.07574
--
16.08
25
1.284
263.654
245.112
0.92942
90.80
76.95
50
2.35
487.82
478.89
0.98189
94.35
92.36
75
3.49
726.85
721.46
0.99271
94.81
127.77
100
4.66
970.53
966.92
0.99636
94.78
172.29
110
5.006
1042.06
1038.81
0.99693
94.70
187.70
240
0
0.381
87.67
4.728
0.05362
--
16.13
25
1.155
272.863
244.46
0.89528
91.15
73.79
50
2.027
484.678
478.99
0.98601
94.37
91.97
75
3.02
725.35
719.45
0.9919
95.10
120.31
100
4.023
966.79
963.65
0.99679
95.12
160.58
110
4.31
1037.72
1035.15
0.99752
95.05
174.97
Note:
System output is initially adjusted to 54 volts DC as measured at the system sense point
at 50% of full load and nominal input. “Percent of Full Load” refers to percent of 17.24
amperes.
Table 7:
Maximum Input Current with 60 Hz Input
Nominal
Input Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
7.5
Note:
At 100% of full load with output adjusted to 58 volts
DC as measured at the output terminals.