Figure 21:
Customer Wiring to the Mating Connector P/N 14190615 (-48 VDC Input Connector)
(Mates to Connector Labeled W in
to
-48 VDC INPUT
Return to terminal 3+.
-48 VDC to terminal 3-.
3+
4+
4-
1+
1-
2+
3-
2-
Pins for wire connections.
Accepts wires in the range
of 22 AWG to 10 AWG.
Sealing cable adapter provided.
Maximum cable diameter is 12.5 mm to
16 mm (0.49” to 0.63”).
The following are some cable choices
that fit this connector:
WR-VG102ST-BRDA, 10/2, 600V from
Rosenberger
HF382 Carolprene SJ00W, 10/2, 300V
from General Cable
Note: Cable choices should be based on
the environment that the power system is
located as well as any National Electrical
Code and local regulations. Choices
above are just examples of cables that
will fit.
P/N 14190615 (-48 VDC Input)
Dust
Cap
Connector
Housing
Sleeve
Sealing
Cable
Adapter
Rear
Pressing
Nut
NOTE! If the sleeve and sealing cable adapter housing
are not separated before installing the cable, the cable
may twist inside the connector housing as the sleeve is
tightened to the connector housing. Perform these steps
in the correct order to prevent this from happening.
1. Strip 7.5 ± 0.5 mm (0.3 ± 0.02 inch)
of insulation off the wires.
2. With the dust cap installed, unscrew the sleeve from
the connector housing to expose the wiring terminals.
3. Remove the rear pressing nut.
4. Separate the sleeve from the sealing cable adapter
housing.
5. Slide the cable(s) through the rear pressing nut,
then through the appropriate opening(s) in the
sealing cable adapter installed in the sealing cable
adapter housing, and finally through the sleeve.
NOTE: If multiple sealing cable adapters are
furnished, select and install the appropriate sealing
cable adapter.
6. Slide the appropriate wires into the appropriate pins
of the connector housing. Tighten the screw in the
connector housing to secure the wire.
Torque to 0.8 N m (7 in-lbs).
7. Tighten the sleeve to the connector housing.
8. Slide the sealing cable adapter housing into the
sleeve.
9. Tighten the rear pressing nut to the sleeve.
Torque to 6.5 N m (58 in-lbs).
Sealing
Cable
Adapter
Housing