Vertiv
|
NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA)
|
Rev. F
32
Figure 18:
Customer Wiring to the Mating Connector P/N 14190607 (AC Input Connector)
(Mates to Connector Labeled X in
to
P/N 14190607 (AC Input)
Dust
Cap
Connector
Housing
Sleeve
Rear
Pressing
Nut
NOTE! If the sleeve and sealing cable adapter housing
are not separated before installing the cable, the cable
may twist inside the connector housing as the sleeve is
tightened to the connector housing. Perform these steps
in the correct order to prevent this from happening.
1. Strip 7.5 ± 0.5 mm (0.3 ± 0.02 inch)
of insulation off the wires.
2. With the dust cap installed, unscrew the sleeve from
the connector housing to expose the wiring terminals.
3. Remove the rear pressing nut.
4. Separate the sleeve from the sealing cable adapter
housing.
5. Slide the cable(s) through the rear pressing nut,
then through the appropriate opening(s) in the
sealing cable adapter installed in the sealing cable
adapter housing, and finally through the sleeve.
NOTE: If multiple sealing cable adapters are
furnished, select and install the appropriate sealing
cable adapter.
6. Slide the appropriate wires into the appropriate pins
of the connector housing. Tighten the screw in the
connector housing to secure the wire.
Torque to 0.8 N m (7 in-lbs).
7. Tighten the sleeve to the connector housing.
8. Slide the sealing cable adapter housing into the
sleeve.
9. Tighten the rear pressing nut to the sleeve.
Torque to 6.5 N m (58 in-lbs).
Sealing
Cable
Adapter
Housing
Two sealing cable adapters provided.
Maximum cable diameter is 8.92 mm to 9.45 mm
(0.35” to 0.37”) for small cable adapter.
Maximum cable diameter is 12.5 mm to 16 mm
(0.49” to 0.63”) large cable adapter.
The following are some cable choices that fit this
connector:
Southwire Royal SJ00W, 14/3, 300V
General Cable HF360 Carolprene SJ00W, 14/3,
300V
Note: Cable choices should be based on the
environment that the power system is located as
well as any National Electrical Code and local
regulations. Choices above are just examples of
cables that will fit.
Sealing
Cable
Adapter
GND
GND
L2/N
L2/N
L1
L1
AC INPUT
Line to terminal L1.
Line/Neutral to terminal L2/N.
Ground to terminal GND.
Pins for wire connections.
Accepts wires in the range
of 22 AWG to 11 AWG.