Circuit Breaker Alarm (P/N 561665 [R48-1000C-5] only)
A circuit breaker alarm activates if the internal circuit breaker opens.
Contacts close between terminals 7 and 8 on the alarm connector during a circuit breaker alarm condition.
Fuse Alarm (P/N 561666 [R48-1000C-6] only)
A fuse alarm activates if any of the internal GMT fuses open.
Contacts close between terminals 7 and 8 on the alarm connector during a fuse alarm condition.
Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC Input and AC Input
Equipment Grounding Connections
The rectifier is equipped with plug-in AC input connectors located on the bottom of the enclosure. Mating
connectors are provided. Customer must provide wiring to the mating connector. See
. Refer also to
. See also “Customer Wiring to the Mating Connectors” starting on page 30.
•
Recommended AC input wire size is 14 AWG.
•
This rectifier requires an external AC input branch circuit protective device rated for 15 A.
-48 VDC Output Connections
WARNING!
Check for correct polarity before making connections.
CAUTION!
Spec. No. 561665 (R48-1000C-5) includes an internal output circuit breaker. This circuit
breaker is shipped in the “ON” position.
The rectifier is equipped with plug-in DC output connectors located on the bottom of the enclosure. Mating
connectors are provided. Customer must provide wiring to the mating connector. See
. See also “Customer Wiring to the Mating Connectors” starting
on page 30.
•
Spec. Nos. 561664 (R48-1000C-4) and 561665 (R48-1000C-5): Recommended DC output wire size is
10 AWG.
•
Spec. No. 561666 (R48-1000C-6): Maximum DC output wire size is 16 AWG.
-48 VDC Input Connections
WARNING!
Check for correct polarity before making connections.
The rectifier is equipped with plug-in -48 VDC input connectors located on the bottom of the enclosure.
Mating connectors are provided. Customer must provide wiring to the mating connector. See
. Refer
also to
. See also “Customer Wiring to the Mating Connectors” starting on page
•
Wire size is determined by site requirements. Maximum -48 VDC input wire size is 10 AWG.