Vertiv
|
NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA)
|
Rev. F
22
INSTALLATION
General Requirements
CAUTION!
PREVENT EQUIPMENT DAMAGE, FROM CONDENSATION
Until the product is turned up for service, the top cover of the product should remained closed as
delivered from the factory. If the top cover of the product is opened when in storage, it shall be placed in
its sealed protective packaging with the provided desiccant bags to prevent condensation. Once the
product is in service, the heat generated by the product is sufficient to prevent humidity build up.
•
This product is intended for installation in network telecommunications facilities (CO, vault, hut or other
electronic equipment enclosure) or as an outside plant cabinet.
•
This product is intended to be connected to the common bonding network in a network
telecommunications facility (CO, vault hut or other equipment enclosure).
•
The DC return connection to this system can remain isolated from system frame and chassis (DC-I).
•
This product is suitable for installation as part of the Common Bonding Network (CBN).
Tools and Test Equipment Required for Installation
The following tools, test equipment and materials are required for the physical installation of the product:
•
Non-Contact Voltage Detector
•
Digital Multimeter (DMM), 0 VDC to 200 VDC, 0 VAC to 300 VAC
•
Torque Wrench
•
Ratchet, 1/2”, 3/8” and 1/4” Drives
•
Socket Set Range from M4 to M13
•
3” and 6” Extensions, 1/4” and1/2” Drive
•
Carpenters Level
•
Lineman’s Scissors
•
Lineman’s Strippers
•
Lineman’s Cutters
•
Crimping Tool with Dies for 6 AWG to 14 AWG
•
Electrician’s Insulated Screwdrivers, Phillips, No. 1 and 2
•
Electrician’s Insulated Screwdrivers, Flat Blade, Small and Large
•
NO-OX-ID or Approved Equivalent