220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Unit Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*35A
MC*35A
FLA
33.5
14.1
with Electric Reheat and Humidifier
FLA
52.1
20.1
with SCR Reheat and Humidifier
3
FLA
75.2
28.0
* Specify disconnect or no disconnect
Notes:
1.
Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2.
Use MM*35E for MM*35K, except with SCR reheat.
3.
SCR Reheat not available with MM*35K.
Table 9.10 Electrical data, 50Hz air-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit (continued)
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Unit
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
Cooling Only
FLA
14.8
19.9
12.7
16.6
—
14.8
—
7.8
WSA
17.8
24.2
15.3
20.2
—
17.8
—
9.4
OPD
25
40
25
30
—
25
—
15
with Electric Reheat
FLA
39.8
44.9
34.4
38.3
—
31.6
—
16.2
WSA
49.1
55.4
42.4
47.3
—
38.8
—
19.9
OPD
50
60
45
50
—
45
—
20
with SCR Reheat
2
FLA
44.0
61.6
38.0
52.7
—
38.9
—
19.9
WSA
54.3
76.3
46.9
65.3
—
47.9
—
24.5
OPD
60
80
50
70
—
50
—
25
with Humidifier
FLA
21.2
26.3
18.4
22.3
—
21.2
—
11.2
WSA
24.2
30.6
21.0
25.9
—
24.2
—
12.8
OPD
35
45
30
40
—
35
—
15
Table 9.11 Electrical data, 60Hz water/glycol-cooled systems using single-point power
kit, evaporator with direct-drive blowers and indoor condensing unit
Vertiv
| Liebert Mini-Mate2—2 and 3 ton Technical Data Manual |
54
Summary of Contents for Liebert Mini-Mate2