220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Evaporator Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*35A
MC*35A
FLA
47.9
18.9
with SCR Reheat
2
FLA
64.6
23.1
with Humidifier
FLA
29.3
12.9
with Electric Reheat and Humidifier
FLA
47.9
18.9
with SCR Reheat and Humidifier
2
FLA
71.0
26.8
* Specify disconnect or no disconnect
Notes:
1.
Use MM*35E for MM*35K, except with SCR reheat.
2.
SCR Reheat not available with MM*35K.
Table 9.9 Electrical data, 50Hz air-cooled systems using
single-point power kit, evaporator with direct-drive
blowers and indoor condensing unit (continued)
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Unit Model Number
MM*35E
MM*35E
Condensing Unit Model Number
MC*35A
MC*35A
Cooling Only
FLA
27.1
10.4
with Electric Reheat
FLA
52.1
20.1
with SCR Reheat
3
FLA
68.8
24.3
with Humidifier
Table 9.10 Electrical data, 50Hz air-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit