208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Unit
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
with Electric Reheat and Humidifier
FLA
39.8
44.9
34.4
38.3
—
31.6
—
16.2
WSA
49.1
55.4
42.4
47.3
—
38.8
—
19.9
OPD
50
60
45
50
—
45
—
20
with SCR Reheat and Humidifier
2
FLA
50.4
68.0
43.7
58.4
—
45.3
—
23.3
WSA
60.7
82.7
52.6
71.0
—
54.3
—
27.9
OPD
70
90
60
80
—
60
—
30
* Specify disconnect or no disconnect
Notes:
1.
Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
2.
SCR Reheat not available with MM*24K or MM*36K.
Table 9.11 Electrical data, 60Hz water/glycol-cooled systems using single-point power
kit, evaporator with direct-drive blowers and indoor condensing unit (continued)
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
Base Evaporator
Model Number
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Condensing Unit
Model Number
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
MC*26W
MC*38W
Cooling Only
FLA
21.2
26.3
16.8
20.7
—
16.8
—
8.5
WSA
24.2
30.6
19.4
24.3
—
19.8
—
10.1
OPD
35
45
25
35
—
30
—
15
with Electric Reheat
FLA
46.2
51.3
38.5
42.4
—
33.6
—
16.9
WSA
55.5
61.8
46.5
51.4
—
40.8
—
20.6
OPD
60
70
50
60
—
45
—
20
with SCR Reheat
3
FLA
50.4
68.0
42.1
56.8
—
40.9
—
20.6
WSA
60.7
82.7
51.0
69.4
—
49.9
—
25.2
OPD
70
90
60
70
—
50
—
30
Table 9.12 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit
Vertiv