Base Evaporator
Model Number
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
208/230 - 3 Ph - 60Hz
460 - 3 Ph - 60Hz
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
MM*24E
MM*36E
Cooling Only
FLA
9.2
9.2
6.4
6.4
—
4.8
—
2.1
WSA
11.5
11.5
8.0
8.0
—
6.0
—
2.6
OPD
20
20
15
15
—
15
—
15
with Electric Reheat
FLA
34.2
34.2
28.1
28.1
—
21.6
—
10.5
WSA
42.8
42.8
35.1
35.1
—
27.0
—
13.1
OPD
45
45
40
40
—
30
—
15
with SCR Reheat
5
FLA
38.4
50.9
31.7
42.5
—
28.9
—
14.2
WSA
48.0
63.6
39.6
53.1
—
36.1
—
17.8
OPD
50
70
40
60
—
40
—
20
with Humidifier
FLA
15.6
15.6
12.1
12.1
—
11.2
—
5.5
WSA
19.5
19.5
15.1
15.1
—
14.0
—
6.9
OPD
25
25
20
20
—
15
—
15
with Electric Reheat and Humidifier
FLA
40.6
40.6
33.8
33.8
—
28.0
—
13.9
WSA
50.8
50.8
42.3
42.3
—
35.0
—
17.4
OPD
60
60
45
45
—
40
—
20
with SCR Reheat
5
and Humidifier
FLA
44.8
57.3
37.4
48.2
—
35.3
—
17.6
WSA
56.0
71.6
46.8
60.3
—
44.1
—
22.0
OPD
60
80
50
70
—
45
—
25
* Specify disconnect or no disconnect
Notes:
1.
Belt drive data includes externally mounted high static blower box, powered from unit.
2.
Use MM*36E electrical data for MM*40C chilled water units.
3.
For units with Hot Water Reheat (available only on MM*40C units), use appropriate values from “Cooling only” or “with Humidifier”
categories.
4.
Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
5.
SCR Reheat not available with MM*24K, MM*36K or MM*40C.
Table 9.2 Belt drive split system evaporator or chilled water electrical data, with high static blower