Liebert Mini-Mate2—2- and 3-Ton
SL-10535a_ REV5_2-17
10
Guide Specifications
The iCOM CMS Web Interface shall be used to register systems to the Mobile Cloud, remotely access
unit-level display settings via a web URL which shall provide read/write capability to the Liebert Mini-
Mate2 system for setpoints, alarms, sensor calibration and other settings found on the unit level display.
2.5.11 Liebert
®
SiteScan
®
Site Monitoring System
A Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote
monitoring of the Liebert Mini-Mate2 unit and monitoring of other Liebert support equipment. The
Liebert SiteScan shall have the capability to monitor and change (at the user direction) the temperature
and humidity setpoints and sensitivities of each unit. The printer shall provide the user with
chronological alarm information. It shall also be capable of being programmed to print out environmental
conditions or operating modes at each unit.
2.5.12 Drycooler
The Liebert
®
drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The
drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil and
multiple direct drive fans. All electrical connections and controls shall be enclosed in an integral weather
resistant electric control panel section of the drycooler. The unit is quiet and corrosion-resistant.
The drycooler shall be designed for _____°F (°C) ambient.
2.5.13 Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The pump
shall be rated for ____ gpm (l/s) at ____ ft. (kPa) of head, and operate on _____ volt, ____ phase,
______ Hz.
3.0 EXECUTION
3.1
INSTALLATION OF AIR CONDITIONING UNIT
3.1.1 General
Install air conditioning unit in accordance with manufacturer's installation instructions. Install unit plumb
and level, firmly anchored in location indicated, and maintain manufacturer’s recommended clearances.
3.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s electrical connection diagram submittal to electrical contractor. Install
and wire per local and national codes.
3.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish
copy of manufacturer’s piping connection diagram submittal to piping contractor.
3.1.4 Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Unit drain shall be trapped internally.
3.1.5 Field-Supplied Pan
A field-supplied pan with drain shall be installed beneath cooling units installed without air distribution
plenum and beneath water/glycol condensing units..
3.2
FIELD QUALITY CONTROL
Startup air conditioning unit in accordance with manufacturer’s startup instructions. Test controls and
demonstrate compliance with requirements.