Base Evaporator Model Number
220 - 1Ph - 50Hz
380/415 - 3Ph-50Hz
MM*35E
MM*35E
Cooling Only
FLA
2.8
1.4
with Electric Reheat
FLA
27.8
11.1
with SCR Reheat
4
FLA
44.6
15.3
with Humidifier
FLA
9.2
5.1
with Electric Reheat and Humidifier
FLA
34.2
14.8
with SCR Reheat and Humidifier
4
FLA
50.9
19.0
* Specify disconnect or no disconnect
Notes:
1.
Use MM*35E electrical data for MM*39C chilled water units.
2.
For units with Hot Water Reheat (available only on MM*39C units), use appropriate values from “Cooling only” or “with
Humidifier” categories.
3.
Use MM*35E for MM*35K, except with SCR reheat.
4.
SCR Reheat not available with MM*35K or MM*39C.
Table 9.3 Direct drive split system evaporator or chilled water electrical data, 50Hz
220 - 1 Ph - 50Hz
380/415 - 3 Ph - 50Hz
Base Evaporator Model Number
MM*35E
MM*35E
Cooling Only
FLA
7.0
2.6
with Electric Reheat
FLA
32.0
12.3
with SCR Reheat
5
FLA
48.7
16.5
with Humidifier
Table 9.4 Belt drive split system evaporator or chilled water electrical data, 50Hz