Liebert® EXL S1

Operation and Maintenance Guide

250kVA – 1200kVA, 60Hz, Three-Phase UPS, Single-Module and Multi-Module 
(Distributed Bypass)

Summary of Contents for Liebert EXL S1

Page 1: ...Liebert EXL S1 Operation and Maintenance Guide 250kVA 1200kVA 60Hz Three Phase UPS Single Module and Multi Module Distributed Bypass...

Page 2: ...disclaims all liability for damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools a...

Page 3: ...22 2 3 1 Startup 1 N Module System 22 2 3 2 Load Transfer 1 N System Transfer System Inverter to Bypass 25 2 3 3 Load Transfer 1 N System Transfer System from Bypass to Inverter 25 2 3 4 Load Transfe...

Page 4: ...ntenance 38 4 3 1 Battery Safety Precautions 38 4 3 2 Torque Requirements 40 4 4 Detecting Trouble 41 4 5 Reporting a Problem 41 4 6 Upstream Feeder Circuit Breaker Setting Inspections 41 5 Specificat...

Page 5: ...properly trained and qualified personnel and in accordance with applicable regulations as well as with manufacturers specifications Be constantly aware that the UPS contains high DC as well as AC vol...

Page 6: ...t d tablir des contacts Le circuit de d rivation les bornes de sortie ASC et le commutateur statique de derivation continueront d afficher une tension c a moins que les disjoncteurs externes associ s...

Page 7: ...binets after initial installation For systems using DC sources other than batteries refer to the manufacturer s recommendations for handling and care ADVERTISSEMENT L arrimage des batteries internes d...

Page 8: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 4 This page intentionally left blank...

Page 9: ...shown in Figure 1 1 below the AC utility source is input at the rectifier and the rectifier converts the AC utility into DC power The inverter converts that DC power from the rectifier or DC power fro...

Page 10: ...one line diagram dual input with static bypass and back feed disconnect Item Description 1 UPS cabinet 2 Bypass AC Input 3 RBB 4 Rectifier AC Input 5 RFB 6 To DC supply 7 AC output Vertiv Liebert EXL...

Page 11: ...Dry Contacts 6 Form C Contacts 4 XP6 AP30 XP3 DP 9 connectors Serial Interface For Service 5 AP30 XP12 Selectable Output Dry Contacts 6 Form C Contacts 6 AP30 XP11 Selectable Input Dry Contacts 8 Form...

Page 12: ...f NOTE If the inverter is asynchronous with the bypass the static switch will transfer the load from the inverter to the bypass WITH interruption in AC power to the critical load This interruption is...

Page 13: ...to allow isolating the UPS from all power sources while continuing to supply power to the critical load Maintenance Bypass use is described in Operation on page 13 1 3 Options NOTE Although solenoid...

Page 14: ...vailable consisting of the number of Vycon flywheel units in separate cabinets necessary to provide the specified operating time Each flywheel unit has an internal circuit breaker for isolating the fl...

Page 15: ...gs Network Interfaces Audible Alarm Silence Enable Disable Automatic Battery Test Enable Disable Test Duration hh mm ss Test Cycle 1 45 days Test Inhibit Time 1 1092 hr Minimum Cell Voltage 1 65 2 9 V...

Page 16: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 12 This page intentionally left blank...

Page 17: ...ll other firmware versions use the instructions detailed in the Operation and Maintenance Guide SL 26090 that applies to your UPS Contact the factory to obtain the relevant document Firmware versions...

Page 18: ...ed disconnect Item Description 1 Maintenance bypass panelboard switchboard 2 UPS cabinet 3 Bypass AC input 4 MBB 5 Optional interlock 6 MIB 7 AC output 8 Module AC output 9 Module AC input 10 BFD 11 T...

Page 19: ...and back feed disconnect for single input UPS Item Description 1 Maintenance bypass panelboard switchboard 2 UPS cabinet 3 Bypass AC input 4 MBB 5 Optional interlock 6 MIB 7 AC output 8 Module AC outp...

Page 20: ...escription 1 Maintenance bypass panelboard switchboard 2 UPS cabinet 3 Bypass AC input 4 MBB 5 Optional interlock 6 MIB 7 AC output 8 Module AC output 9 To DC supply 10 RFB 11 Module rectifier AC inpu...

Page 21: ...input UPS Item Description 1 Maintenance bypass panelboard switchboard 2 UPS cabinet 3 Bypass AC input 4 MBB 5 Optional interlock 6 MIB 7 AC output 8 Module AC output 9 To DC supply 10 Module Rectifi...

Page 22: ...are versions for each UPS module can be identified via the Touchscreen Control Panel Starting the Unit Without Power Supplied to the Connected Load If the installation includes a Maintenance Bypass po...

Page 23: ...nstalled is in the Open position 2 Close the external rectifier feeder breaker External Remote Back feed Breaker RBB for single input feed applications External Rectifier Feed Breaker RFB for dual inp...

Page 24: ...ass Re Transfer Procedure 1 From the Touchscreen Control Panel touch OPERATE UNIT OPERATIONS Inverter On Single 2 Verify that the critical load transfers from the UPS bypass to the UPS inverter 2 2 3...

Page 25: ...e Bypass Load Transfers Single Module System If Load is on Maintenance Bypass 1 Verify that power is available to the module s bypass and rectifier inputs 2 Verify that the UPS is started and in Bypas...

Page 26: ...e sure that personnel and equipment are ready for the critical load distribution system to be energized ADVERTISSEMENT Risque de d charge lectrique pouvant entra ner des dommages mat riels des blessur...

Page 27: ...to start a 1 N Module System with and without remote breakers The Touchscreen Control Panel will list all steps required for the process based on the unit s operational status and other factors Startu...

Page 28: ...tart at this time Do not proceed until the Touchscreen Control Panel is fully operational on each UPS 4 Verify that the rectifier has started on each UPS that will be added to the collective bus The r...

Page 29: ...verter 2 3 4 Load Transfer 1 N System Remove a UPS from System Collective NOTE UPS modules must be de energized with MOB open or be in Test Operation Mode once removed from the collective bus 1 Verify...

Page 30: ...ective will remain Off if the collective bus is on Inverter but will turn On if the collective bus is on BYPASS 5 Close the external Module Battery Disconnect s MBD on the UPS module 6 Close the exter...

Page 31: ...bypass and cannot be re transferred to the inverter until the key is reinserted 3 If using a key interlock system insert the key into the lock for the Maintenance Bypass Breaker MBB retract the bolt...

Page 32: ...ge Failure to close the MIB will interrupt power to the load 6 Open the Maintenance Bypass Breaker MBB The load is now on UPS internal bypass 7 If using a key interlock system remove the key from the...

Page 33: ...and optional internal Back Feed Disconnect BFD on each UPS if installed 6 Open the external Rectifier Feeder Breaker for each UPS in the system External Remote Back Feed Breaker RBB for single input...

Page 34: ...will start at this time Do not proceed until the Touchscreen Control Panel is fully operational 2 Verify that the rectifier has started The rectifier icon on the Touchscreen Control Panel should be gr...

Page 35: ...BB for the UPS system 5 Transfer the UPS system to Inverter see Load Transfer 1 N System Transfer System from Bypass to Inverter on page 25 The UPS system can now be load bank tested 6 Once load bank...

Page 36: ...all UPS modules are connected to the collective bus 2 8 Transformer Energization The Liebert EXL S1 features a rugged inverter design such that a like size transformer can be energized while the UPS i...

Page 37: ...Red An alarm has occurred at the UPS Table 3 1 RAS Indicators The RAS also includes An audible alarm Lamp Test Reset push button to test the LED indicators Audio Reset push button to silence an audib...

Page 38: ...Fault Some regulatory agencies require a system to detect battery DC ground faults in ungrounded DC systems Generally this applies to DC systems both battery and flywheel systems field wired to the UP...

Page 39: ...bles Ne remplacez aucun composant sans l autorisation expresse du Vertiv Assurez vous que les armoires d ASC sont exemptes de mat riaux trangers tels que des r sidus de soudure des bouts de c ble etc...

Page 40: ...strument de test d entrer en contact physique ou lectrique avec la terre En cas d incendie impliquant de l quipement lectrique n utiliser que des extincteurs au dioxyde de carbone ou autres extincteur...

Page 41: ...zed in the UPS have a limited life cycle To prevent a wear out failure of one of these components affecting the critical load operations we recommend that these components be periodically inspected an...

Page 42: ...sity Periodic inspections of battery and terminal voltages specific gravity and connection resistance should be made Strictly follow the procedures in the battery manufacturer s manual See battery man...

Page 43: ...es batteries associ es cet quipement Soyez conscient en tout temps que le syst me de batteries contient des tensions lev es c c et c a V rifiez si une tension est pr sente l aide de voltm tres c c et...

Page 44: ...eurs si l armoire doit ventuellement tre repositionn e ou d plac e NOTE Do not use cleaners on the batteries Solvents can make the battery cases brittle Use only a dry cloth or a cloth moistened in wa...

Page 45: ...ate malfunction or impending malfunction A daily check of the control panel will help provide an early detection of problems Refer to the Liebert EXL S1 Touchscreen Control Panel SL 26094 to interpret...

Page 46: ...ving high availability from the UPS For further information regarding proper trip settings for the feeder breakers contact Vertiv Technical Support NOTE The instantaneous trip setting of the breaker f...

Page 47: ...d DC Parameters Battery Type Lithium Ion VRLA Valve Regulated Lead Acid VLA Vented Lead Acid Nominal Battery Bus VDC 480 Battery Float Voltage VDC 540 DC Ripple at Float Voltage 1 0 RMS value 3 4 Vpp...

Page 48: ...perating Altitude ft m Up to 3300 1000 without derating Acoustical Noise dBA 78 72 at partial load General and System Data Inverter Type High Efficiency Transformer Free IGBT Three Level PWM Inverter...

Page 49: ...2009 2269 1030 500 600 500 600 480 63 x 36 x 79 1 1600 x 914 x 2009 2450 1111 500 600 500 600 480 x 74 8 x 36 x 79 1 1900 x 914 x 2009 2749 1247 500 600 500 600 480 x 2749 1247 500 600 500 600 480 x x...

Page 50: ...Dimensions and Weights With and Without Options continued Parameter Specification Enclosure The UPS is housed in a NEMA 1 enclosure The enclosure is designed for indoor use only and is not to be subj...

Page 51: ...2 28 152 330 130 155 130 90 130 40 130 600 125 210 125 115 125 47 125 110 110 207 110 77 102 Based on nominal input voltage and no battery charging Table 5 4 Current versus time curves of inverter ove...

Page 52: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 48 This page intentionally left blank...

Page 53: ...with a common battery the Stop command is present on some but not all the units Battery Status Battery Non Blocking Fault 04 054 Set when a non blocking fault is active in the stage Battery Status Bat...

Page 54: ...ss Bypass Status Bypass Non Blocking Fault 01 042 Set when a non blocking fault is active in the stage Bypass Status Bypass Global On Request 01 078 Bypass Static Switch On command request on the shar...

Page 55: ...At least one non blocking fault is active Charger Booster Status DC Bus Too LowTo Charge 03 061 General Status Warning pending 00 000 Set when at least one stage in the core is in warning General Stat...

Page 56: ...ive Not yet defined General Status General Core Non Blocking Fault 00 176 Set when a customer non blocking fault in stage is set not yet defined General Status Manual Mode Command Pending 00 200 Set w...

Page 57: ...l CR 06 079 Inverter Status Intelligent Parallel CR 06 079 Inverter Status Intelligent Parallel CR 06 079 Inverter Status Operation ECO mode 06 086 Active if inverter is turning On the load is on Bypa...

Page 58: ...hen a non blocking fault is present in the actual stage not yet implemented MUN Status MUN has a warning 08 000 Set when at least one MUN stage is in warning MUN Status MUN has a fault 08 001 Set when...

Page 59: ...s off 02 000 Rectifier Status Rectifier is turning on 02 001 Rectifier Status Rectifier is on 02 002 Rectifier Status Rectifier fault 02 004 Set either blocking or non blocking Rectifier Status Rectif...

Page 60: ...24 017 RBM temperature probe is not responding Temp T 10 C or T 50 C or RBM Sensor Status bit 3 2 11 Battery Alarm Battery Switch Wiring Fault 24 056 Core only Set when the RBM option is installed wi...

Page 61: ...100V fix threshold Control always active independently to Battery breaker status Inhibits starting the battery charger Charger Booster Alarm Buck Booster DC Voltage Low 23 056 Booster inhibit when DC...

Page 62: ...0 165 General Alarm PIB Overtemperature 20 166 General Alarm Cable Conduit Overtemperature 20 167 General Alarm MIB Overtemperature 20 168 General Alarm Duplicated Parallel Unit Id 20 169 General Alar...

Page 63: ...hed 100 This triggers the request to transfer to bypass with default configuration Inverter Alarm Overtemperature Phase U A 26 101 Set when Phase Utemperature is greater than the value specified by P...

Page 64: ...Status UPS Time not valid 08 026 Set when date is 1 Jan 2009 MUN Status Life call in progress 08 033 Call in progress MUN Status Life call rescheduled 08 034 Call rescheduled MUN Status Life modem not...

Page 65: ...ns is out of limits Rectifier Status pre charge in progress 02 011 Hold off delay and resistor pre charge Rectifier Status Walk in in progress 02 012 Rectifier current limit ramp Rectifier Status pre...

Page 66: ...temperature Phase W C 22 063 Set when Phase W temperature is greater then P 1151 setting Def 80 C Rectifier Alarm Overtemperature B Phase U A 22 073 Set when Phase Utemperature is greater then P 1151...

Page 67: ...oster Fault Charger Redundant Voltage error 33 022 If the absolute value of the difference between primary and secondary battery voltage acquisition is greater than a predefined threshold a fault is i...

Page 68: ...eneral Fault Incorrect power class 30 036 General Fault DSP Signal Hardware Failure 30 049 General Fault DSP Signal Hardware Failure 30 049 General Fault DSP Signal Hardware Failure 30 049 General Fau...

Page 69: ...hen Current limit condition occurs at inverter start while the output voltage is ramping up Current limit condition lasts more then 200 ms Current limit condition set again after 2nd Dynamic line Supp...

Page 70: ...e sensor fault SW detected based on M I value outside sensor limit interval 15 C T 150 C for 60 seconds P 780 23 Inverter Fault Temp Probe Broken Phase W C 36 106 Inverter temperature sensor fault SW...

Page 71: ...Choke B Ph V B 36 135 Inverter filter overtemperature Any of Thermal Switch ALA M I XP31 Pin 4 9 active Inverter Fault Overtemperature Choke B Ph W C 36 136 Inverter filter overtemperature Any of The...

Page 72: ...e Ph U A 32 067 Rectifier filter overtemperature Any of Thermal Switch ALA M I XP31 Pin 1 6 active Rectifier Fault Overtemperature Choke Ph V B 32 068 Inverter filter overtemperature Any of Thermal Sw...

Page 73: ...Probe B Broken Phase W C 32 087 Rectifier temperature sensor fault SW detected based on M I value outside sensor limit interval 15 C T 150 C for 60 seconds P 1780 6 Rectifier Fault Overtemperature Ch...

Page 74: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 70 This page intentionally left blank...

Page 75: ...0V ES1 18 S022 600kVA kW ES1 18 S007 625kVA kW ES1 18 S008 750kVA kW ES1 18 S009 800kVA kW ES1 18 S001 1000kVA kW ES1 18 S002 1100kVA kW ES1 18 S003 1200kVA kW Inverter DC AC Efficiency ES1 18 S063 25...

Page 76: ...052 300kVA kW ES1 18 S049 400kVA kW 415V ES1 18 S053 400kVA KW 480V ES1 18 S050 500kVA KW 415V ES1 18 S054 500kVA KW 480V ES1 18 S055 600kVA KW ES1 18 S056 625kVA KW ES1 18 S057 750kVA KW ES1 18 S058...

Page 77: ...29186 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S062 S MAJOR MODULE AC AC EFFICIENCY TYPICAL SMS AND 1 N 250kVA 250kW 480V 60Hz LIEB...

Page 78: ...29186 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S019 S MAJOR MODULE AC AC EFFICIENCY TYPICAL SMS AND 1 N 300kVA 300kW 480V 60Hz LIEB...

Page 79: ...CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S025 LIEBERT EXL S1 415V 60Hz 1 OF...

Page 80: ...29186 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S020 S MAJOR MODULE AC AC EFFICIENCY TYPICAL SMS AND 1 N 400kVA 400kW 480V 60Hz LIEB...

Page 81: ...CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S026 LIEBERT EXL S1 415V 60Hz 1 OF...

Page 82: ...CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S021 LIEBERT EXL S1 480V 60Hz 1 OF...

Page 83: ...CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S022 LIEBERT EXL S1 480V 60Hz 1 OF...

Page 84: ...URCE CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S007 LIEBERT EXL S1 480V 60Hz 1...

Page 85: ...URCE CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S008 LIEBERT EXL S1 480V 60Hz 1...

Page 86: ...URCE CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S009 LIEBERT EXL S1 480V 60Hz 1...

Page 87: ...URCE CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S001 LIEBERT EXL S1 480V 60Hz 1...

Page 88: ...RCE CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S002 LIEBERT EXL S1 480V 60Hz 1...

Page 89: ...RCE CONNECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S003 LIEBERT EXL S1 480V 60Hz 1...

Page 90: ...29186 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S063 S MAJOR MODULE DC AC EFFICIENCY TYPICAL SMS AND 1 N 250kVA 250kW 480V 60Hz LIEB...

Page 91: ...29186 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S027 S MAJOR MODULE DC AC EFFICIENCY TYPICAL SMS AND 1 N 300kVA 300kW 480V 60Hz LIEB...

Page 92: ...SION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S033 LIEBERT EXL S1 415V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 11 16 2...

Page 93: ...29186 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S028 S MAJOR MODULE DC AC EFFICIENCY TYPICAL SMS AND 1 N 400kVA 400kW 480V 60Hz LIEB...

Page 94: ...SION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S034 LIEBERT EXL S1 415V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 11 16 2...

Page 95: ...SION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S029 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 11 16 2...

Page 96: ...SION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S030 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 11 16 2...

Page 97: ...ION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S010 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 02 09 20...

Page 98: ...ION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S011 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 02 09 20...

Page 99: ...ION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S012 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 02 09 20...

Page 100: ...EVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S004 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 1 06 2...

Page 101: ...EVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S005 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 1 06 2...

Page 102: ...EVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S006 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S MAJOR J SHIPMAN 1 06 2...

Page 103: ...86 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S064 S MAJOR MODULE ECO MODE AC AC EFFICIENCY TYPICAL SMS AND 1 N 250kVA 250kW 480V 60Hz...

Page 104: ...86 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S035 S MAJOR MODULE ECO MODE AC AC EFFICIENCY TYPICAL SMS AND 1 N 300kVA 300kW 480V 60Hz...

Page 105: ...NECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S041 LIEBERT EXL S1 415V 60Hz 1 OF 1 S...

Page 106: ...86 COLUMBUS OH 43229 0 1 16 2020 JASON ZHANG 1 OF 1 JASON ZHANG ECN NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S036 S MAJOR MODULE ECO MODE AC AC EFFICIENCY TYPICAL SMS AND 1 N 400kVA 400kW 480V 60Hz...

Page 107: ...NECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S042 LIEBERT EXL S1 415V 60Hz 1 OF 1 S...

Page 108: ...NECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S037 LIEBERT EXL S1 480V 60Hz 1 OF 1 S...

Page 109: ...NECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S038 LIEBERT EXL S1 480V 60Hz 1 OF 1 S...

Page 110: ...ECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S014 LIEBERT EXL S1 480V 60Hz 1 OF 1 S M...

Page 111: ...ECTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S015 LIEBERT EXL S1 480V 60Hz 1 OF 1 S M...

Page 112: ...CTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S016 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MA...

Page 113: ...CTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S017 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MA...

Page 114: ...CTED TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S018 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MA...

Page 115: ...NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S051 S MAJOR MODULE DYNAMIC ONLINE VI MODE AC AC EFFICIENCY TYPICAL SMS AND 1 N 250kVA 250kW 480V 60Hz LIEBERT EXL S1 NOTES 1 NO LOAD POWER LOSS 2 8kW 2 ME...

Page 116: ...NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S052 S MAJOR MODULE DYNAMIC ONLINE VI MODE AC AC EFFICIENCY TYPICAL SMS AND 1 N 300kVA 300kW 480V 60Hz LIEBERT EXL S1 NOTES 1 NO LOAD POWER LOSS 2 8kW 2 ME...

Page 117: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S049 LIEBERT EXL S1 415V 60Hz 1 OF 1 S MAJOR S...

Page 118: ...NO REF DWG TM FORM NO DPN004658 Rev0 ES1 18 S053 S MAJOR MODULE DYNAMIC ONLINE VI MODE AC AC EFFICIENCY TYPICAL SMS AND 1 N 400kVA 400kW 480V 60Hz LIEBERT EXL S1 NOTES 1 NO LOAD POWER LOSS 2 8kW 2 ME...

Page 119: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S050 LIEBERT EXL S1 415V 60Hz 1 OF 1 S MAJOR S...

Page 120: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S054 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 121: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S055 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 122: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S056 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 123: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S057 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 124: ...TITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S058 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 125: ...ITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S059 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 126: ...ITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S060 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 127: ...ITLE DATE LATEST REV REVISION DRAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S061 LIEBERT EXL S1 480V 60Hz 1 OF 1 S MAJOR S...

Page 128: ...ET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S045 LIEBERT EXL S1 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 06 01 2018 FOR ALL kVA INVERTER OVERLOAD CHART NOTES 1 OVE...

Page 129: ...RAWN BY DESIGNED BY APPROVED BY SHEET NO ECN NO REF DWG DWG NO TM 1050 DEARBORN DR P O BOX 29186 COLUMBUS OH 43229 ES1 18 S046 LIEBERT EXL S1 1 OF 1 S MAJOR S MAJOR J SHIPMAN 0 06 01 2018 FOR ALL kVA...

Page 130: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide...

Page 131: ...er names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Gr...

Reviews: