5.4.2 Bottom Connection
Open the rear door and remove filters. For details on removing filters, see
on page 31 . Unscrew the soft pipe
from the humidifier supply copper pipe and route the soft pipe through the pump drainage hole and humidifier water inlet
hole on the base plate to your water supply system.
NOTE: The end of the humidifier supply pipe is G 3/4" connector. You can use the convertor provided in the
accessories bag to convert the connector to Rc 1/2".
Figure 5.10 Bottom Connection for Humidifier
Item
Description
Item
Description
1
Rear door
3
Water inlet pipe connection
2
Humidifier
4
Pump drainage hole and humidifier water inlet hole
5 Piping Connections