Figure 5.6 Top Connection (CRC60)
Item
Description
Item
Description
1
Rear door
3
Chilled water inlet connection
2
Pump drainage connection
4
Chilled water outlet connection
5.2.3 Bottom Connection
To connect water inlet and outlet pipes through the bottom panel:
1.
Open the rear door and remove filters. For details on removing filters, see
2.
Remove the humidifier together with the support bracket (only for CRC30).
a. Loosen the hose clamp and disconnect stream pipe from the top of the humidifier.
b. Disconnect the electrode wires from the top of the humidifier.
c. Disconnect the level sensor cables from the top of the humidifier.
d. Unscrew the soft pipe from the bottom of the humidifier.
e. Loosen the hose clamp and disconnect the water supply pipe under the humidifier.
5 Piping Connections
34
Vertiv™ Liebert® CRV CRC30 and CRC60 Chilled Water Cooling System User Manual