7 - 24
Heat Rejections (A version)
Liebert CRV - PD - 265086 - 11.01.2018
Tab. 7d - Technical data and performance of air-cooled condenser Liebert HCR
Model
Power
supply
[V/Ph/Hz]
Total Heat
Rejection
(THR)*
R410A
[kW]
Air
Volume
[m
3
/h]
Noise
Level **
[dB(A)] @
5 m, f.f.
Input
Power
[kW]
Current
Absorp tion
[A]
FLA
[A]
Refrigerant
connections
[mm]
Dimensions
[mm]
Weight
[kg]
Gas line
[mm]
Liquid
line
[mm]
HCR17 230/1/50
17.0
4410
44.5
0.27
1.2
1.2
16
16
W 1120
D 856
H 934
60
HCR24 230/1/50
23.98
8600
50.0
0.55
2.5
2.6
16
16
W 1340
D 831
H 1112
60
HCR33 230/1/50
32.2
7400
50.0
0.55
2.5
2.6
16
16
W 1340
D 831
H 1112
75
HCR43 230/1/50
46.0
17000
53.0
1.10
5.0
5.2
16
16
W 2340
D 831
H 1112
92
HCR51 230/1/50
52.0
17000
53.0
1.10
5.0
5.2
22
16
W 2340
D 831
H 1112
93
HCR59 230/1/50
62.0
15600
53.0
1.10
5.0
5.2
22
16
W 2340
D 831
H 1112
102
HCR76 230/1/50
78.0
25500
55.0
1.65
7.5
7.8
22
16
W 3340
D 831
H 1112
136
HCR88 230/1/50
92.0
23400
55.0
1.65
7.5
7.8
22
16
W 3340
D 831
H 1112
165
HCR99 230/1/50
130.0
32000
57.0
2.20
10.0
10.0
28
22
W 4338
D 831
H 1112
220
Summary of Contents for Liebert CRV 300 CW
Page 2: ......