7 - 27
Heat Rejections (A version)
Liebert CRV - PD - 265086 - 11.01.2018
Model
Power
supply
[V/Ph/Hz]
Total Heat
Rejection
(THR)*
R410A
[kW]
Air
Volume
[m
3
/h]
Noise
Level **
[dB(A)] @
5 m, f.f.
Input
Power
[kW]
Current
Absorp tion
[A]
FLA
[A]
Refrigerant
connections
[mm]
Dimensions
[mm]
Weight
[kg]
Gas
line
[mm]
Liquid
line
[mm]
MCS028 230/1/50
29.6
7452
50.10
0.47
1.73
2.30
22
22
W 1283
D 1180
H 955
70
MCM035 230/1/50
34.50
8000
50.10
0.47
1.73
2.30
22
22
W 1381
D 972
H 1269
105
MCM040 230/1/50
44.78
10600
52.00
0.78
3.75
440
22
22
W 1381
D 972
H 1269
105
MCL055 400/3/50
58.60
16250
53.50
1.60
3.60
4.40
28
28
W 1676
D 1509
H 1105
156
MCM070 230/1/50
69.00
16000
53.10
0.94
3.46
8.80
35
35
W 2602
D1269
H 972
200
MCM080 230/1/50
89.56
21200
55.00
1.55
7.50
8.80
35
35
W 2602
D1269
H 972
200
MCL110 400/3/50
117.20
32500
57.00
3.20
7.20
8.80
35
35
W 3102
D 1509
H 1102
273
MCM160 230/1/50
179.12
42400
6,000
3.10
15.00
17.60
28
28
W 5045
D 1269
H 972
380
MCL165 400/3/50
175.80
48750
66.80
4.80
10.8
13.2
35
35
W 4527
D 1509
H 1105
404
Tab. 7g - Technical data and performance of air-cooled condenser Liebert MC Basic
Summary of Contents for Liebert CRV 300 CW
Page 2: ......