6 - 17
Specifications
Liebert CRV - PD - 265086 - 11.01.2018
Cond. Temp. 45°C
CR011RA
CR021RA
28°C DB - 45% RH
Net Total kW
11.3
19.7
Net Sensible kW
10.7
17.9
Unit Power Input kW
3.57
6.01
Heat rejection kW
14.87
25.71
Supply Air Temperature °C
16.1
14.8
25°C DB - 45% RH
Net Total kW
10.7
18.9
Net Sensible kW
10.6
17.7
Unit Power Input kW
3.77
6.40
Heat rejection kW
14.37
25.30
Supply Air Temperature °C
13.3
12
25°C DB - 40% RH
Net Total kW
10.4
18.6
Net Sensible kW
10.4
18.6
Unit Power Input kW
3.78
6.53
Heat rejection kW
14.18
25.13
Supply Air Temperature °C
13.5
11.2
22°C DB - 55% RH
Net Total kW
10.4
18.6
Net Sensible kW
8.9
15.1
Unit Power Input kW
3.78
6.53
Heat rejection kW
14.18
25.13
Supply Air Temperature °C
12.4
11.1
22°C DB - 50% RH
Net Total kW
10.1
18.3
Net Sensible kW
9.4
16.1
Unit Power Input kW
3.79
6.60
Heat rejection kW
13.89
24.9
Supply Air Temperature °C
11.8
10.3
Summary of Contents for Liebert CRV 300 CW