7 - 25
Heat Rejections (A version)
Liebert CRV - PD - 265086 - 11.01.2018
Model
Power
supply
[V/Ph/Hz]
Total Heat
Rejection
(THR)*
R410A
[kW]
Air
Volume
[m
3
/h]
Noise
Level **
[dB(A)] @
5 m, f.f.
Input
Power
[kW]
Current
Absorp tion
[A]
FLA
[A]
Refrigerant
connections
[mm]
Dimensions
[mm]
Weight
[kg]
Gas line
[mm]
Liquid
line
[mm]
HCR24 400/3/50
23.75
8600
53.0
0.55
1.3
1.3
16
16
W 1340
D 831
H 1112
60
HCR33 400/3/50
31.49
7400
53.0
0.55
1.3
1.3
16
16
W 1340
D 831
H 1112
75
HCR43 400/3/50
45.84
17000
56.0
1.10
2.4
2.4
16
16
W 2340
D 831
H 1112
92
HCR51 400/3/50
51.5
17000
56.0
1.10
2.4
2.4
22
16
W 2340
D 831
H 1112
93
HCR59 400/3/50
61.03
15600
56.0
1.10
2.4
2.4
22
16
W 2340
D 831
H 1112
102
HCR76 400/3/50
78.0
25500
58.0
1.65
3.6
3.6
22
16
W 3340
D 831
H 1112
136
HCR88 400/3/50
92.0
23400
58.0
1.65
3.6
3.6
22
16
W 3340
D 831
H 1112
165
HCR99 400/3/50
116.5
33200
59.0
2.20
4.8
4.8
28
22
W 4338
D 831
H 1112
220
Tab. 7e - Technical data and performance of air-cooled condenser Liebert HCR 3ph