User Manual 10H52258UM60 - Rev. 3 - 01/2019
60
APM 400/600
Introducing UPS Operations
The UPS will automatically restart and enable output power only when the following conditions are met:
•
Auto-recovery mode configured in the event of EOD.
•
If the UPS has been set-up so that there is specific delay time following a shut down due to EOD (by default,
the delay time in the UPS is 10 minutes), once this delay period has elapsed, the UPS restarts the bypass and
then the inverter. During the delay time, the UPS will charge its batteries to provide a safety margin for
equipment shutdown if the mains input fails again.
•
Sometimes the Auto recovery after EOD is disabled. If so, users may have to restart the UPS manually by
pressing the FAULT CLEAR key first for 2 seconds and the INVERTER ON key for 2-3 seconds.
Warning
Manual start-up is disabled during the automatic restart process. Automatic restart must be configured by
authorized Vertiv engineers using the Vertiv configuration software.
6.10
Selecting the Language
The LCD menu and data display is available in 13 languages:
•
Simplified Chinese
•
Traditional Chinese
•
English
•
French
•
German
•
Italian
•
Japanese
•
Polish
•
Portuguese
•
Spanish
•
Swedish
•
Czech
•
Turkish.
in order to select your language of choice, proceed as follows:
•
On the Output menu screen, press the F3 (left) or F4 (right) key to select the Language menu.
•
Press the HELP (Enter) key to move the cursor to the screen data window.
•
Press the F3 (up) or F4 (down) key to select the desired language.
•
Press the HELP (Enter) key to continue.
•
Press the F2 (ESC) key to return repeatedly to return to the Output menu.
At this point the LCD displays all the menus in the selected language.
6.11
Changing the Current Date and Time
To change the system date and time, proceed as follows:
•
On the Output menu screen, press the F3 (left) or F4 (right) key to select the Settings menu.
•
Press the HELP (Enter) key to move the cursor to the screen data window.
•
Press the F3 (up) or F4 (down) key to select the Date and Time item. Press the HELP (Enter) key to confirm
•
Press the F3 ( up) or F4 (down) keys to scroll to the row displaying the date and time. Press the HELP (Enter)
key to confirm.
•
Use the F3 (up) or F4 (down) to enter the current date and time.
•
Press the HELP (Enter) key to confirm. Press the F2 (Esc) key to return to the Output menu.
6.12
Password management
The system provides password protection for the UPS operation and control. The default password is 12345. In
order to execute the UPS self-test or battery test, it is necessary to enter the correct credentials in the Password
field.
To change the password, proceed as follows:
•
On the Output menu screen, press the F3 (left) or F4 (right) key to select the Settings menu.
•
Press the HELP (Enter) key to move the cursor to the screen data window.