30
Vertiv I Liebert ITA2 30kVA I Manual
2.7.4
Battery Mode Start-Up
1. Close the battery MCB, and press the power button on the UPS front panel for two seconds,
the LCD displays the startup screen. The alarm indicator will be yellow and the buzzer will
continuously beep after the rectifier finishes the startup.
2. Press the power button for two seconds, the LCD prompts a dialogue box shown in
Figure 2-2
1
.
Status
Settings
Control
Log
About
Maintain
Confirm
No
Yes
Turn on UPS?
Figure 2-21 Turning on UPS
After selecting 'YES', the inverter starts, and the run indicator (green) is on.