Vertiv I Liebert ITA2 30kVA I Manual
8.3
Communication Cables
Communication cable is compulsory in parallel system. See Table 8-
3
for cable description.
Refer to
3.4.2 Connecting Parallel Cables
for the methods to connect the parallel cables.
Table 8-3
Description of the communication cable
Type
Name
Description
Appearance
ITA-20k00A
L3A02C00L
1
Parallel
communiation
cable
For N + 1 parallel system, N + 1
communication cables (1m) are needed. For
example, two communication cables are
needed in 1 + 1 parallel system; three
communicatio cables are needed in 2 + 1
parallel system; four communication cables
are needed in 3 + 1 parallel system
ITA-20k00A
L3A02CL3
Parallel
communiation
cable
For N + 1 parallel system, N + 1
communication cables (3m) are needed. For
example, two communication cables are
needed in 1 + 1 parallel system; three
communicatio cables are needed in 2 + 1
parallel system; four communication cables
are needed in 3 + 1 parallel system
8.4
Guide Rail
The guide rail is used in rack installation of UPS, POD (optional). The detailed description is
listed in Table 8-
4
.
Table 8-4 Description of the guide rail
Type
Name
Description
Appearance
GXT4-RMKI
T1832
Guide rail for rack
installation
A set of guide rail includes a left guide rail
and a right guide rail, and its bearing is
50kg. Use the guide rail in the rack
installation. It is applicable to the various
server cabinet, UPS, and POD
For the rack mode installation procedure, refer to
2.5.2 Rack Installation.