Specific Methods Of Creating ADFs
4200-002
90
Revision 6
Figure 179. Hydrometer Interface
Align the data logger and computer IR ports, press
.
Set ...Starting at Cell Number nn to the cell number the hydrometer
should start downloading data to, typically one. Thus, hydrometer Cell 1
data is recorded in the file under Cell 1, and so on.
NOTE:
Change the starting cell number when more than one
hydrometer records data from the same battery. For
example, on a 256
–cell battery, one hydrometer tests cells
1 to 128 and stores the data in hydrometer locations 1 to
128. The other hydrometer tests cells 129 to 256 and stores
in 1 to 128 as well. Capture the first hydrometer with the
starting cell number set to one and capture the second into
the same file with the starting number set to 129.
Set the
Read Date for this Data Set
. Type a date or click the
drop–down calendar button.
Set the
Temperature Unit in Hydrometer
box to C or F to
agree with how hydrometer temperature readings were made.
CAUTION:
This setting does not convert the readings from C to F or
from F to C.
To start capturing, click
.